7 Timer Function
Notes:
• Before using the timer function as a control method, set the AOP real time clock as described
in the Set Time/Date section.
• Setting a timing event for ‘every day’, configures the same event for each day of the week
separately. To clear an ‘every day’ event, you must clear the event individually from each day.
• When multiple events must be cleared from the Timer function, it may be easier to reset the
AOP as described in the AOP Reset section.
• When in MASTER mode of operation and viewing the connected SED2 drives, a ‘T’ displays in
the top left corner to indicate that the connected SED2 drives are under timed remote control
and may start or stop unexpectedly.
• To start or stop an attached SED2 VSD with the AOP timer function you must set the com-
mand source parameters P0700[0]=4 and P0700[1]=4 (USS on BOP link or AOP).
7.1 Setting the AOP Timer
When in LOCAL or MASTER mode, you can access the timer feature from the main menu. The timer operates
as a 7-day, time-of-day, on/off controller (much like a central heating controller but with the addition of a possi-
ble multi-VSD selection).
Key Function
Moves down through the available choices of the highlighted field.
Moves up through the available choices of the highlighted field.
Press this key to confirm a changed field and to move the cursor to the next field.
Press this key for several seconds to move the cursor back to the previous field.
Cancels the current settings and returns the user to the main menu.
All changes will be discarded.
Cancels the entire timer event currently displayed.
0.…31
Available USS SED2 drive network settings. In MASTER mode, 0 through 31 are
selectable when the AOP detects the SED2 at that address.
B
Allows the programmed timing event to be communicated to all connected SED2
drives (in broadcast mode).
This is the ON symbol and indicates that the currently viewed or programmed
event is when the SED2 drive is switched on.
This is the OFF symbol and indicates that the currently viewed or programmed
event is when the SED2 drive is switched off.
In general, use the following keys to set the timer:
• Press
to confirm the input.
•
and to scroll through input ranges.
• Press
to cancel the input and to return to the previous entry.