User Manual

18/32
Siemens Building Technologies SED2 Advanced Operator Panel AOP CM1B5192en
HVAC Products Editing Parameters 19.01.2004
5.6.2 Wait Request
Certain tasks that the SED2 performs take longer than other tasks. If this occurs, a screen (such as the follow-
ing) displays to inform you that the SED2 is completing a task.
Upread
To Param. Set 00
Please wait..
Fn
Fn
5.6.3 Parameter Download
The download procedure writes a parameter set stored in the AOP to any SED2 VSD connected in LOCAL
mode or to a single specified SED2 VSD on a network of SED2 VSDs connected in MASTER mode. In MAS-
TER mode, the download procedure must select a specific SED2 VSD as the recipient SED2 VSD. (The
download cannot simultaneously occur in all networked SED2 VSDs.)
Use the following procedure to download a parameter set:
1. From the main menu, use
and to scroll through the list of options and to highlight the DOWNLOAD
item.
Press
to confirm the selection. Press to cancel the download process.
The AOP displays a DOWNLOAD menu.
Note: In MASTER mode, the AOP prompts for selection of a specific SED2 VSD from a list of the net-
worked SED2 VSDs.
2. Use
and to scroll through the list of parameter sets and to highlight the parameter set from which
information will be copied.
Press
to confirm the selection.
3. The AOP displays a confirmation screen.
Press
to confirm the selection. Press to cancel the download process.
4. The AOP displays a wait screen while the download process occurs.
5. On completion of the download process, the AOP returns to the main menu.
Notes:
If the download fails, perform the following:
1. Reset VSD parameters: Commissioning Parameter P0010=30 for factory settings and Fac-
tory Reset Parameter P0970=1 to reset all parameters to their default values.
2. Cycle VSD power off/on.
3. Repeat the download process.