User Manual
11/32
Siemens Building Technologies SED2 Advanced Operator Panel AOP CM1B5192en
HVAC Products AOP Start-Up & Initialization 19.01.2004
Use and to set P1000[1]=1 motor potentiometer [MOP] setpoint.
Press
to confirm the setting and the cursor returns to the parameter.
6. Use
and to scroll through the parameters and to highlight Commissioning parameter P0010.
Press
to confirm the selection and the cursor advances to the parameter value.
Use
and to set P0010[0]=0 (Ready) to exit the quick commissioning mode.
Press
to confirm the setting and the cursor returns to the parameter.
7. Use
and to scroll through the parameters and to highlight USS Telegram Off Time P2014.
Press
to confirm the selection and the cursor advances to the parameter index.
Use
and to scroll through the indexes for P2014 and to highlight P2014[1] (index 1, Serial Interface
BOP Link). Press
to confirm the selection and the cursor advances to the parameter value.
Use
and to set P2014[1]=5000 (USS on BOP/AOP local link) to prevent unexpected drive opera-
tion. In this mode, removal of the AOP from the SED2 VSD causes a timeout to occur in 5 seconds.
Press
to confirm the setting and the cursor returns to the parameter.
8. Press
to return to r0000. Press to display the standard (OPERATE) screen.
9. Press
to switch the SED2 to HAND mode.
10. Press
to start the SED2.
11. Use
to increase the output; Use to decrease the output.
The AOP displays the current status of the SED2 and motor. The following table explains information on this
display.
STOPPED
r0000
I=0.0A
M=0%
F=0.00Hz
RPM=0
V=0.0V
Fn
P
The following table explains the Status Information of an AOP Display with an Operating SED2.
Data Description
STOPPED Indicates the motor connected to the SED2 is not running (pulses disabled).
RUNNING Indicates the motor connected to the SED2 is running (pulses enabled).
FAULT
Indicates a fault condition has occurred. The SED2 is not running. A fault, described by
the AOP under the DIAGNOSTICS menu, is preventing operation.
WARNING
The SED2 has detected a problem in normal operation and is informing you of the drive
condition.
INHIBIT
A previously occurring fault or OFF condition is preventing SED2 operation. Sending an
OFF1 command from the currently active command source clears this condition.
r0000 Indicates a read-only parameter. Drive Display r0000 is the normal operating display.
F= 0.00 Hz Indicates the frequency at which the SED2 VSD/motor is running.
S= 0.00 Hz Indicates the speed (frequency) when the motor last stopped.
I= 0.0 A Indicates the output current.
RPM= 0 Indicates the speed of the motor.
M= 0% Indicates the current torque of the motor.
V= 0.0 V Indicates the output voltage.
Vdc= 0.0V Indicates the dc link voltage.
Indicates the direction of the running motor.