User Manual
10/32
Siemens Building Technologies SED2 Advanced Operator Panel AOP CM1B5192en
HVAC Products AOP Start-Up & Initialization 19.01.2004
3.5 Quick Commissioning
Note: Simultaneously press and , at any time, to display the main men
The following table describes the main menu items.
Menu Item Description
OPERATE Displays the current status of the SED2 VSD/motor.
DIAGNOSTICS Displays a recent fault history.
PARAMETERS
Allows you to select a parameter group (similar to Parameter Filter P0004) and to
configure individual parameters.
MODE Allows you to select the AOP mode of operation as follows:
– LOCAL
– MASTER
– INTERNAL
– SLAVE
– PC mode
UPREAD
(UPLOAD)
Allows you to read a parameter set from a SED2 VSD to the AOP.
DOWNLOAD Allows you to write a parameter set from the AOP to a SED2 VSD.
LANGUAGE Allows you to select a new language for the AOP display.
SETUP Allows you to customize the configuration of the AOP.
TIMER Allows you to set a start and stop time for SED2 VSD operation.
1. Use
and to scroll through the list of options and to highlight the PARAMETERS item.
Press
to confirm the selection.
The AOP prompts to select the desired parameter group. Use
and to scroll through the list of op-
tions and to highlight the All parameters item. Press
to confirm the selection.
Note: The chapter Editing Parameters, provides an overview of parameter access levels and a proce-
dure for editing parameters.
2. Use
and to scroll through the parameters and to highlight User Access Level Parameter P0003.
Press
to confirm the selection and the cursor advances to the parameter value.
Use
and to set P0003=3 (Expert level).
Press
to confirm the setting and the cursor returns to the parameter.
3. Use
and to scroll through the parameters and to highlight Commissioning Parameter P0010.
Press
to confirm the selection and the cursor advances to the parameter value.
Use
and to set P0010=1 (Quick Commissioning).
Press
to confirm the setting and the cursor returns to the parameter.
4. Use
and to scroll through the parameters and to highlight Command Source P0700.
Press
to confirm the selection and the cursor advances to the parameter index.
Use
and to scroll through the indexes for P0700 and to highlight P0700[1] (index 1).
Press
to confirm the selection and the cursor advances to the parameter value.
Use
and to set P0700[1]=4 (USS on BOP/AOP local link).
Press
to confirm the setting and the cursor returns to the parameter.
5. Use
and to scroll through the parameters and to highlight Frequency Setpoint P1000.
Press
to confirm the selection and the cursor advances to the parameter index.
Use
and to scroll through the indexes for P1000 and to highlight P1000[1] (index 1).
Press
to confirm the selection and the cursor advances to the parameter value.