SCALANCE X-100 1 ___________________ Introduction 2 ___________________ Network topologies SIMATIC NET Industrial Ethernet switches SCALANCE X-100 3 ___________________ Description of the device 4 ___________________ Assembly 5 ___________________ Connecting up Maintenance and 6 ___________________ troubleshooting Operating Instructions 7 ___________________ Technical specifications 8 ___________________ Certifications and approvals 9 ___________________ Dimension drawings 07/2014 A2B00060666-05
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 Introduction ............................................................................................................................................. 5 1.1 On the Operating Instructions ........................................................................................................ 5 1.2 On the product ............................................................................................................................... 7 2 Network topologies ..................
Table of contents 7 Technical specifications ........................................................................................................................ 41 7.1 SCALANCE X104-2 .................................................................................................................... 41 7.2 SCALANCE X106-1 .................................................................................................................... 44 7.3 SCALANCE X108 ......................................
1 Introduction 1.1 On the Operating Instructions Purpose of the Operating Instructions These Operating Instructions support you when commissioning networks with the Industrial Ethernet switches of the SCALANCE X-100 product line.
Introduction 1.1 On the Operating Instructions Audience These Operating Instructions are intended for persons who commission networks with the IE switches of the SCALANCE X-100 product line. SIMATIC NET glossary Explanations of many of the specialist terms used in this documentation can be found in the SIMATIC NET glossary. You will find the SIMATIC NET glossary here: ● SIMATIC NET Manual Collection or product DVD The DVD ships with certain SIMATIC NET products.
Introduction 1.2 On the product 1.2 On the product What is possible? The devices of the SCALANCE X100 product line allow the cost-effective installation of Industrial Ethernet bus and star structures with switching functionality.
Introduction 1.
Introduction 1.2 On the product Unpacking and checking WARNING Do not use any parts that show evidence of damage If you use damaged parts, there is no guarantee that the device will function according to the specification. If you use damaged parts, this can lead to the following problems: • Injury to persons • Loss of the approvals • Violation of the EMC regulations • Damage to the device and other components Use only undamaged parts. 1. Make sure that the package is complete. 2.
Introduction 1.
Network topologies 2 Switching technology allows extensive networks to be set up with numerous nodes and simplifies network expansion. Which topologies can be implemented? Using the IE switches of the SCALANCE X-100 product line, you can implement star topologies. Note Keep to the maximum permitted cable lengths of the devices you are using. You will find the permitted cable lengths in the section "Technical specifications (Page 41)".
Network topologies Figure 2-2 Example of an electrical/optical star topology with SCALANCE X112-2 and SCALANCE X104-2 SCALANCE X-100 12 Operating Instructions, 07/2014, A2B00060666-05
3 Description of the device 3.1 Table 3- 1 Overview of the SCALANCE X-100 Overview of the product characteristics Device type SCALANCE X104-2 X106-1 X108 X108PoE X112-2 X116 X124 SIMATIC environment + + + + + + + Diagnostics LED + + + + + + + 24 VDC + + + + + + + 2 x 24 VDC + + + + + + + Compact housing (securing collar, etc.
Description of the device 3.2 Product properties 3.2 Product properties 3.2.1 SCALANCE X104-2 Possible connections The SCALANCE X104-2 has four RJ-45 jacks and two BFOC sockets for the connection of end devices or other network segments. Note The BFOC socket (Bayonet Fiber Optic Connector) corresponds to the ST socket.
Description of the device 3.2 Product properties 3.2.2 SCALANCE X106-1 Possible connections The SCALANCE X106-1 has six RJ-45 jacks and a BFOC socket for the connection of end devices or other network segments. Note The BFOC socket (Bayonet Fiber Optic Connector) corresponds to the ST socket.
Description of the device 3.2 Product properties 3.2.3 SCALANCE X108 Possible connections The SCALANCE X108 has eight RJ-45 jacks for the connection of end devices or other network segments.
Description of the device 3.2 Product properties 3.2.4 SCALANCE X108PoE Possible connections The SCALANCE X108 PoE has eight RJ-45 jacks for the connection of end devices or other network segments. Ports 1 to 2 do not have the PoE function. Figure 3-4 SCALANCE X108PoE Power over Ethernet (PoE) function The PoE function allows the power supply of connected Ethernet devices via the Ethernet cable so that the end device does not need a separate power supply.
Description of the device 3.2 Product properties 3.2.5 SCALANCE X112-2 Possible connections The SCALANCE X112-2 has twelve RJ-45 jacks and two BFOC sockets for the connection of end devices or other network segments. Note The BFOC socket (Bayonet Fiber Optic Connector) corresponds to the ST socket.
Description of the device 3.2 Product properties 3.2.6 SCALANCE X116 Possible connections The SCALANCE X116 has 16 RJ-45 jacks for the connection of end devices or other network segments.
Description of the device 3.2 Product properties 3.2.7 SCALANCE X124 Possible connections The SCALANCE X124 has 24 RJ-45 jacks for the connection of end devices or other network segments.
Description of the device 3.3 TP ports (twisted pair) 3.3 TP ports (twisted pair) RJ-45 connector pinout With SCALANCE X-100, the twisted-pair port is designed as an RJ-45 jack with MDI-X pin assignment (Medium Dependent Interface Autocrossover) of a network component.
Description of the device 3.3 TP ports (twisted pair) Note Permitted cable lengths TP cords or TP-XP cords with a maximum length of 10 m can be connected to the TP port with the RJ-45 jack. With the IE FC cables and IE FC RJ-45 plugs 180, an overall cable length of a maximum of 100 m is permitted between two devices depending on the cable type.
Description of the device 3.4 FO port (fiber optic) 3.4 FO port (fiber optic) Transmission speed The transmission speed of the optical Fast Ethernet ports is 100 Mbps. Transmission technique The transmission mode for 100Base-FX is specified in the IEEE 802.3 standard. Since the full duplex mode and the transmission rate cannot be modified for optical transmission, autonegotiation cannot be selected. Transmission medium Data transmission is over multimode fiber-optic cable (FO cable).
Description of the device 3.5 LEDs 3.5 LEDs Fault LED "F" (red LED) The fault LED indicates the incorrect functioning of the device. LED color LED status Meaning Red Lit The SCALANCE switch X-100 detects a fault. At the same time, the signaling contact opens. The following faults/errors are detected: 1. Link down event on a monitored port. 2. Loss of the power supply of one of the two redundant power supplies or the power supply drops below 14 V. 3.
Description of the device 3.6 SET button 3.6 SET button Function With the SET button, you can display and change the set fault mask. Setting the fault mask Factory setting When supplied (factory defaults), the fault mask is set so that the power supply L1+/M1 is monitored. No ports are monitored. If you connect a power supply to L2+/M2, adapt the fault mask accordingly: Clear the error LED and the signaling contact or set the fault mask to the power supply L2+/M2.
Description of the device 3.6 SET button Note If an empty fault mask is set or needs to be set, the 2 port LEDs flash alternately. If the fault mask is empty, no port is monitored. Note The PoE voltage at the PoE ports cannot be monitored using the fault mask.
4 Assembly 4.1 Types of installation The devices can be installed in the following ways: ● Installation on a 35 mm DIN rail ● Installation on a SIMATIC S7-300 standard rail ● Wall mounting WARNING Ambient temperature between 55 °C and 60 °C If a device is operated in an ambient temperature of more than 55 °C, the temperature of the device housing may be higher than 70 °C.
Assembly 4.2 Installation on a DIN rail 4.2 Installation on a DIN rail Installation To install the device on a 35 mm DIN rail complying with DIN EN 50022, follow the steps below: 1. Place the second housing guide of the device on the top edge of the DIN rail. 2. Press the device down against the DIN rail until the spring catch locks in place. 3. Fit the connectors for the power supply. See also section "Power supply (Page 33)". 4. Fit the connectors for the signaling contacts.
Assembly 4.2 Installation on a DIN rail Uninstalling To remove the device from the DIN rail, follow the steps below: 1. Disconnect all connected cables. 2. Release the DIN rail catch on the bottom of the device using a screwdriver. 3. Pull the lower part of the device away from the DIN rail.
Assembly 4.3 Installation on a standard rail 4.3 Installation on a standard rail Installation on a SIMATIC S7-300 standard rail To install the device on an S7-300 standard rail, follow the steps below: 1. Place the first housing guide of the device on the top edge of the S7-300 standard rail. 2. Screw the device to the underside of the standard rail (tightening torque 2 Nm). 3. Fit the connectors for the power supply. See also section "Power supply (Page 33)". 4.
Assembly 4.4 Wall mounting 4.4 Wall mounting To mount the device on a wall, you require the following: ● 4 wall plugs, 6 mm in diameter and 30 mm long ● 4 screws 3.5 mm in diameter and 40 mm long To mount the device on a wall, follow the steps below: 1. Prepare the drill holes for wall mounting. For the precise dimensions, refer to the section "Dimension drawings (Page 67)". 2. Fit the connectors for the power supply. See also section "Power supply (Page 33)". 3.
Assembly 4.
5 Connecting up 5.1 Power supply The power supply is connected using a 4-pin plug-in terminal block. The power supply can be connected redundantly. Both inputs are isolated. There is no distribution of load. When a redundant power supply is used, the power supply unit with the higher output voltage supplies the device alone. The power supply is connected over a high resistance with the enclosure to allow an ungrounded set up. The two power supplies are non-floating.
Connecting up 5.1 Power supply WARNING The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a Limited Power Source (LPS). This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1 must be connected to the power supply terminals. The power supply unit for the equipment power supply must comply with NEC Class 2, as described by the National Electrical Code (r) (ANSI / NFPA 70).
Connecting up 5.2 Signaling contact 5.2 Signaling contact The signaling contact is connected to a 2-pin plug-in terminal block. The signaling contact (relay contact) is a floating switch with which error/fault states can be signaled by breaking the contact. NOTICE Damage due to voltage being too high The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low voltage SELV, 24 VDC).
Connecting up 5.3 Grounding 5.3 Grounding Installation on a DIN rail The device is grounded over the DIN rail. S7 standard rail The device is grounded over its rear panel and the neck of the screw. Wall mounting The device is grounded by the securing screw in the unpainted hole. Note that the device must be grounded over a securing screw with as low a low resistance as possible. If the device is mounted on a non-conductive base, a grounding cable must be fitted.
Connecting up 5.4 IE FC RJ-45 Plug 180 Plugging in the IE FC RJ45 Plug 180 Plug the IE FC RJ45 Plug 180 into the twisted-pair port of the device until it locks in place. Figure 5-2 Plugging in the IE FC RJ45 Plug 180 With its tight fit and locking mechanism with the PROFINET-compliant male connector IE FC RJ45 Plug 180, the securing collar on the TP port of the device ensures a rugged node attachment that provides strain and bending relief for the RJ-45 jack.
Connecting up 5.
Maintenance and troubleshooting 6.1 6 Possible sources of problems and how to deal with them Fuses Some of the Industrial Ethernet switches of the SCALANCE X-100 product line have a resettable fuse / PTC. If the fuse triggers (all LEDs are off despite correctly applied power supply), the device should be disconnected from the power supply for approximately 30 minutes before turning it on again.
Maintenance and troubleshooting 6.
Technical specifications 7.
Technical specifications 7.1 SCALANCE X104-2 Technical specifications Optical parameters Cable type Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm Permitted cable length (glass FO cable) Cable cross-section Attenuation Permitted cable length • 62.5/125 μm • 0 to 4000 m • 50/125 μm • 0 to 5000 m ≤ 1 dB/km at 1300 nm 1200 MHz x km at 1300 nm 6 dB max.
Technical specifications 7.1 SCALANCE X104-2 Technical specifications Installation options • Installation on a DIN rail • Installation on an S7-300 standard rail • Wall mounting Switching properties Aging time 30 seconds Max. number of learnable MAC addresses 2048 Response to LLDP frames Blocking Response to spanning tree BPDU frames Forwarding QoS priority queues 4 Note The number of SCALANCE X Industrial Ethernet switches connected in a line influences the frame delay time.
Technical specifications 7.2 SCALANCE X106-1 7.
Technical specifications 7.2 SCALANCE X106-1 Technical specifications Optical parameters Cable type Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm Permitted cable length (glass FO cable) Cable cross-section Attenuation Permitted cable length • 62.5/125 μm • 0 to 4000 m • 50/125 μm • 0 to 5000 m ≤ 1 dB/km at 1300 nm 1200 MHz x km at 1300 nm 6 dB max.
Technical specifications 7.2 SCALANCE X106-1 Technical specifications Installation options • Installation on a DIN rail • Installation on an S7-300 standard rail • Wall mounting Switching properties Aging time 30 seconds Max. number of learnable MAC addresses 2048 Response to LLDP frames Blocking Response to spanning tree BPDU frames Forwarding QoS priority queues 4 Note The number of SCALANCE X Industrial Ethernet switches connected in a line influences the frame delay time.
Technical specifications 7.3 SCALANCE X108 7.3 Table 7- 3 SCALANCE X108 Technical specifications of the SCALANCE X108 Technical specifications Order number SCALANCE X108 6GK5108-0BA00-2AA3 Connection to Industrial Ethernet Number 8 Design RJ-45 jacks with MDI-X pinning Properties Half / full duplex Transmission speed 10/100 Mbps Permitted cable lengths (Industrial Ethernet) Alternative combinations per length range 0 to 55 m • Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180 • Max.
Technical specifications 7.3 SCALANCE X108 Technical specifications Permitted ambient conditions Ambient temperature During operation -20 °C to +70 °C During storage -40 °C to +80 °C During transportation -40 °C to +80 °C Relative humidity During operation ≤ 95 % no condensation Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C ambient temperature ≤ 3,000 m above sea level at max.
Technical specifications 7.3 SCALANCE X108 Note Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2 You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the type plate.
Technical specifications 7.4 SCALANCE X108PoE 7.4 Table 7- 4 SCALANCE X108PoE Technical specifications of the SCALANCE X108PoE Technical specifications Order number SCALANCE X108PoE 6GK5108-0PA00-2AA3 Connection to Industrial Ethernet Number 8 Design RJ-45 jacks with MDI-X pinning Properties Half / full duplex Transmission speed 10/100 Mbps Permitted cable lengths (Industrial Ethernet) Alternative combinations per length range 0 to 55 m • Max.
Technical specifications 7.4 SCALANCE X108PoE Technical specifications Permitted ambient conditions Ambient temperature During operation -20 °C to +60 °C During storage -40 °C to +80 °C During transportation -40 °C to +80 °C Relative humidity During operation ≤ 95 % no condensation Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C ambient temperature ≤ 3,000 m above sea level at max.
Technical specifications 7.4 SCALANCE X108PoE Note The number of SCALANCE X Industrial Ethernet switches connected in a line influences the frame delay time. When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by the store and forward function of the switch • with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps) • with a 1500 byte frame length by approx.
Technical specifications 7.5 SCALANCE X112-2 7.
Technical specifications 7.5 SCALANCE X112-2 Technical specifications Optical parameters Cable type Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm Permitted cable length (glass FO cable) Cable cross-section Attenuation Permitted cable length • 62.5/125 μm • 0 to 4000 m • 50/125 μm • 0 to 5000 m ≤ 1 dB/km at 1300 nm 1200 MHz x km at 1300 nm 6 dB max.
Technical specifications 7.5 SCALANCE X112-2 Technical specifications Switching properties Aging time 30 seconds Max. number of learnable MAC addresses 2048 Response to LLDP frames Blocking Response to spanning tree BPDU frames Forwarding QoS priority queues 4 Note The number of SCALANCE X Industrial Ethernet switches connected in a line influences the frame delay time.
Technical specifications 7.6 SCALANCE X116 7.6 Table 7- 6 SCALANCE X116 Technical specifications of the SCALANCE X116 Technical specifications Order number SCALANCE X116 6GK5116-0BA00-2AA3 Connection to Industrial Ethernet Number 16 Design RJ-45 jacks with MDI-X pinning Properties Half / full duplex Transmission speed 10/100 Mbps Permitted cable lengths (Industrial Ethernet) Alternative combinations per length range 0 to 55 m • Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180 • Max.
Technical specifications 7.6 SCALANCE X116 Technical specifications Permitted ambient conditions Ambient temperature During operation -20 ℃ to +70 ℃ During storage -40 ℃ to +80 ℃ During transportation -40 ℃ to +80 ℃ Relative humidity During operation ≤ 95 % no condensation Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C ambient temperature ≤ 3,000 m above sea level at max.
Technical specifications 7.6 SCALANCE X116 Note Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2 You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the type plate.
Technical specifications 7.7 SCALANCE X124 7.7 Table 7- 7 SCALANCE X124 Technical specifications of the SCALANCE X124 Technical specifications Order number SCALANCE X124 6GK5124-0BA00-2AA3 Connection to Industrial Ethernet Number 24 Design RJ-45 jacks with MDI-X pinning Properties Half / full duplex Transmission speed 10/100 Mbps Permitted cable lengths (Industrial Ethernet) Alternative combinations per length range 0 to 55 m • Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180 • Max.
Technical specifications 7.7 SCALANCE X124 Technical specifications Permitted ambient conditions Ambient temperature During operation -20 ℃ to +70 ℃ During storage -40 ℃ to +80 ℃ During transportation -40 ℃ to +80 ℃ Relative humidity During operation ≤ 95 % no condensation Operating altitude During operation ≤ 2,000 m above sea level at max. 56 ℃ ambient temperature ≤ 3,000 m above sea level at max.
Technical specifications 7.7 SCALANCE X124 Note Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2 You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the type plate.
Technical specifications 7.
8 Certifications and approvals The SIMATIC NET products described in these Operating Instructions have the approvals listed below. Note Issued approvals on the type plate of the device The specified approvals apply only when the corresponding mark is printed on the product. You can check which of the following approvals have been granted for your product by the markings on the type plate. EMC directive The devices meet the requirements of the EC Directive 2004/108/EC "Electromagnetic Compatibility".
Certifications and approvals Notes for the Manufacturers of Machines The devices are not machines in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 2006/42/EC for these devices. If the devices are part of the equipment of a machine, they must be included in the declaration of conformity procedure by the manufacturer of the machine.
Certifications and approvals IECEx The SIMATIC NET products meet the requirements of explosion protection according to IECEx. IECEx classification: Ex nA IIC T4 Gc DEK 14.
Certifications and approvals Mechanical stability (in operation) Device DIN EN 60068-2-6 oscillation DIN EN 60068-2-6 oscillation DIN EN 60068-2-6 oscillation DIN EN 60068-2-29 permanent shock DIN EN 60068-2-29 permanent shock 10 - 58 Hz: 0.075 mm 10 - 58 Hz: 0.15 mm 5 - 8.51 Hz: 3.5 mm 100 m/s2, 16 ms duration 250 m/s2, 6 ms duration 100 shocks per axis 1000 shocks per axis 58 - 500 Hz: 10 m/s2 58 - 500 Hz: 20 10 cycles m/s2 10 cycles 8.
Dimension drawings Figure 9-1 9 Dimension drawing, rear of the SCALANCE X104-2, X106-1, X108, X108PoE SCALANCE X-100 Operating Instructions, 07/2014, A2B00060666-05 67
Dimension drawings Figure 9-2 Dimension drawing, rear of the SCALANCE X116, X112-2 SCALANCE X-100 68 Operating Instructions, 07/2014, A2B00060666-05
Dimension drawings Figure 9-3 Dimension drawing, rear of the SCALANCE X124 SCALANCE X-100 Operating Instructions, 07/2014, A2B00060666-05 69
Dimension drawings Figure 9-4 Dimension drawing, side view SCALANCE X-100 70 Operating Instructions, 07/2014, A2B00060666-05
Dimension drawings Figure 9-5 Dimension drawing, bending radii SCALANCE X-100 Operating Instructions, 07/2014, A2B00060666-05 71
Dimension drawings SCALANCE X-100 72 Operating Instructions, 07/2014, A2B00060666-05
Index A Accessories, 8 Approvals, 63 Auto polarity exchange, 22 Autonegotiation, 22 B Bending radii, 71 BFOC socket ST socket, 15 Error/fault, 26 Factory setting, 25 FO port, 23 Further documentation, 5 G Glossary, 6 Grounding, 36 Installation on a DIN rail, 36 S7 standard rail, 36 Wall mounting, 36 I C CE mark, 63 Components of the product, 8 Connection to Industrial Ethernet, 41, 44, 47, 50, 53, 56, 59 Connector pinout, 21 SCALANCE X108 PoE, 21 IE FC RJ-45 Plug 180, 36 Installation, 36 Plugging in, 3
Index Optical parameters, 42, 45, 54 Order numbers, 41, 44, 47, 50, 53, 56, 59 P Permitted ambient conditions, 42, 45, 48, 51, 54, 57, 60 Permitted cable lengths, 22, 41, 44, 47, 50, 53, 56, 59 Possible attachments SCALANCE X108, 16 Possible connections SCALANCE X104-2, 14 SCALANCE X106-1, 15 SCALANCE X108PoE, 17 SCALANCE X112-2, 18 SCALANCE X116, 19 SCALANCE X124, 20 Power over Ethernet (PoE) function, 17 Power supply, 33 Product properties, 13 R Reduced voltage, 39 RJ-45, 21 S SCALANCE X104-2 Connecti
Index SCALANCE X104-2, 41 SCALANCE X106-1, 44 SCALANCE X108, 47 SCALANCE X108PoE, 50 SCALANCE X112-2, 53 SCALANCE X116, 56 SCALANCE X124, 59 TP ports, 21 SCALANCE X-100 Operating Instructions, 07/2014, A2B00060666-05 75
Index SCALANCE X-100 76 Operating Instructions, 07/2014, A2B00060666-05