Basic Documentation

21 / 87
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Smart Infrastructure Engineering 2020-01-30
2.7.2 Rotary actuators SQL.. to SAL..
SQL.. SAL..
Pos. time [s] Torque [Nm] Pos. time [s] Torque [Nm]
SQL31.. SQL31.10 120 12,5 SAL31.00T10 120 10
SQL32.. SQL32.10 125 12,5 SAL31.00T10 120 10
SQL32.12 70 12,5 SAL31.00T10 or 120 10
SAL31.03T10
1)
30 10
SQL32.13 30 5 SAL31.03T10 30 10
SQL33.. SQL33.00 125 12,5 SAL31.00T10 120 10
SQL33.03 30 10 SAL31.03T10 30 10
SQL83.. SQL83.00 125 12,5 SAL81.00T10 120 10
SQL83.04 30 10 SAL81.03T10 30 10
SQL35.. SQL35.00 125 20 SAL31.00T20
2)
120 20
SQL35.00 125 20 SAL31.00T40
2)
120 40
SQL85.. SQL85.00 125 20 SAL81.00T20
2)
120 20
SQL85.00 125 20 SAL81.00T40
2)
120 40
1)
SAL.. positioning time differs from that of SQL32.12 and SQL32.13 rotary actuators. Consider
positioning time when replacing.
2)
use SAL.T20 on VKF46.40, VKF46.50 and VKF46.65
use SAL.T40 on VKF46.80, VKF46.100 and VKF46.125
Rotary actuators SQL.. SAL..
SAL31.00T10
SAL31.03T10
SQL33.. SQL35.. SAL81.00T10 SAL31.00T20 SAL31.00T40
SQL31.. SQL32.. SQL83.. SQL85.. SAL81.03T10 SAL81.00T20 SAL81.00T40
VBF21..
DN 40 / DN 50
1)
- - ASK32 - ASK32N -
1)
-
1)
DN 65…150 - - ASK31 - ASK31N - -
VBF31..
DN 40 / DN 50
2)
- - ASK32 - ASK32N -
2)
-
2)
DN 65…100 - - ASK31 - ASK31N - -
B3f..
DN 40 / DN 50
2)
Direct ASK25 ASK31 - - - -
DN 65…150 Direct ASK25 ASK31 - ASK31N - -
C1f..
DN 40 / DN 50
2)
Direct - ASK31 - - - -
DN 65…100 Direct - ASK31 - ASK31N - -
K1i.. DN 20…32 Direct ASK24 ASK33 - ASK33N - -
K1f.. DN 40…200 Direct ASK24 ASK33 - ASK33N - -
VKF41..
DN 40…125 - - ASK33 - ASK33N - -
DN 150 / DN 200 - - ASK33 ASK35 ASK33N - ASK33N
VKF45.. DN40…65 - - - ASK35 - ASK35N ASK35N
DN80...200 - - ASK35N
1)
Replace with rotary actuators SQK34.., SQK84.. (data sheet N4508) or SQK33.00 (data sheet
N4506).
2)
Replace with rotary actuators SQK33.00 + ASK32
D Rotary actuators SAL.. are not suited for mounting sets ASK24, ASK25, ASK31,
ASK32, ASK33, ASK35, ASK40 and ASK41.
2.7.3 Electrical accessories
· If an auxiliary switch is required, its switching point should be indicated on the
plant schematic.
· For media below 0 °C the stem heating element ASZ6.6 keeps the valve free
from freezing.
· For this case, do not insulate the actuator bracket and the valve stem, as air
circulation must be ensured!
· Non-observance of the above may result in accidents and fires!
· Do not touch the hot parts without prior protective measures to avoid
burns.
Note
Notes