Data Sheet for Product

9
Siemens CE1N4509en
Smart Infrastructure 2020-11-26
Technical data
Power
Operating voltage
SAX31P03 AC 230 V ±15%
SAX61P03..
AC 24 V ± 20 % / DC 24 V +20 % / -15 % (SELV /
PELV)
SAX81P03
Frequency 45...65 Hz
External supply line fusing (EU) Non-renewable fuse 6...10 A slow
Circuit break max. 13 A, tripping characteristic B, C,
D to EN 60898
Power source with current limitation of max. 10 A
Power consumption at 50 Hz
SAX31P03
Stem
retracts/extends
6.5 VA / 4 W
SAX61P03 9.5 VA / 4.5 W
SAX61P03/MO 10.2 VA / 5 W
SAX81P03 7 VA / 4.5 W
Typical inrush current
1)
(3-position actuators)
SAX31P03 2.3 A
SAX81P03 4.5 A
Operating data
Positioning times (with the specified nominal stroke) The positioning time may vary depending on the type of
valve
(Type summary [➙ 3])
SAX31P03, SAX61P03, SAX81P03 30 s
Positioning force 500 N
Nominal stroke 20 mm
Permissible media temperature (valve fitted) 1...120 °C
Signal inputs
Positioning signal ”Y”
SAX31P03, SAX81P03 3-position
SAX31P03 Voltage AC 230 V ±15%
SAX81P03 AC 24 V ± 20% / DC 24 V + 20% / - 15%
SAX61P03
DC 0...10 V
Power consumption 0.1 mA
Input impedance 100 kΩ
DC 4...20 mA
Power consumption DC 4...20 mA ± 1%
Input impedance 500 kΩ