ACVATIX™ Electromotoric actuators for valves SAX..P.. Actuators with 20 mm stroke and 500 N force ● ● ● ● ● ● ● CE1N4509en 2020-11-26 SAX31P03 Operating voltage AC 230 V, 3-position positioning signal SAX61P03 Operating voltage AC/DC 24 V, positioning signal 0...10V, 4...
Use Electromotoric actuators to operate Siemens combi valves for type series VPF43.., VPF44.. and VPF53.. with 20 mm stroke, as control valves on ventilation, air conditioning, district heating and refrigeration plants. Functions Function Description 3-position control A 3-position signal controls the actuator via connection terminals Y1 or Y2. The desired position is transmitted to the valve. Modulating control The modulating positioning signal provides stepless motor control.
Type summary Type Item No. Stroke SAX31P03 1) S55150-A118 SAX61P03 2) S55150-A114 Positio- Operating ning force voltage Positioning signal AC 230 V 3-position Spring return time Positioing time LED Manual adjustment 3) Auxiliary functions - 4) DC ...10 V SAX61P03/MO 2) SAX81P03 2) 20 mm 500 N AC 24 V DC 24 V S55150-A143 S55150-A116 DC 4...20 mA - 0...
Spare parts Product number / Stock number Housing cover Screw (valve stem coupling) U-bracket 8000060843 Equipment combinations VPF43.. Valve type DN H100 [mm] m100 Δpmin [m3/h] [m3/h] [kPa] Min. VPF43.50F16 S55266-V100 50 2.3 15 Standard flow VPF43.65F24 S55266-V102 65 4.4 25 VPF43.80F35 S55266-V104 80 5.3 34 VPF43.50F25 S55266-V101 50 4.3 25 High flow rate VPF43.65F35 S55266-V103 65 6 35 VPF43.80F45 S55266-V105 80 7 43 20 Data sheet 35 N4315 70 VPF44..
Product documentation Title Contents Document ID Actuators SAX.., SAY.., SAV.., SAL.. for valves Basic documentation: CE1P4040en Detailed information on stroke actuators including Modbus types Stroke actuators for valves with 15/20/40 mm stroke and rotary actuators for butterfly valves Electromotoric actuators for valves SA.., Modbus RTU Data sheet: A6V101037195 Mounting instructions G..161../MO and S..
Engineering SAX31P03 / SAX81P03 3-position actuators must be controlled by a controller, see Connection diagrams [➙ 15]. SAX61P03 Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA. Modulating actuators have an input impedance of 100 kΩ. SAX61P03/MO The Modbus converter is designed for analog control at 0...10 V. Keep the analog signal setting on the actuator as is (switch 1 to OFF); adjustment not permitted. ASZ7.5 Actuators with a DC 0...9.
Mounting Mounting positions Indoor application Outdoor application 1) 2) 1) Only together with weather shield ASK39.2. IP54 housing protection remains unchanged. 2) SA../MO is not intended for outdoor use. Operation Direction of control action On valves where the stem retracts to the close position, "direct acting" means that the value is fully closed at positioning signal Y = 0 V or Z = 0 Ω (i.e. 100 %). Direct acting Y, Z Positioning signal V Volume flow Positioning signal Y DC 0...10 V, 4...
Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations. Warranty service Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations".
Technical data Power Operating voltage SAX31P03 AC 230 V ±15% SAX61P03.. AC 24 V ± 20 % / DC 24 V +20 % / -15 % (SELV / PELV) SAX81P03 Frequency 45...65 Hz External supply line fusing (EU) ● Non-renewable fuse 6...10 A slow ● Circuit break max. 13 A, tripping characteristic B, C, D to EN 60898 ● Power source with current limitation of max. 10 A Power consumption at 50 Hz SAX31P03 6.5 VA / 4 W SAX61P03 9.5 VA / 4.5 W SAX61P03/MO Stem retracts/extends SAX81P03 10.2 VA / 5 W 7 VA / 4.
Communication SAX61P../MO Communication protocol Modbus RTU RS-485, not galvanically isolated Number of nodes Max. 32 Address range 1...248 / 255 Factory setting Transmission formats 255 1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2 Factory setting 1-8-E-1 Factory setting Auto Baud rates (kbaud) Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.
Environmental conditions Operation IEC 60721-3-3 Climatic conditions Class 3K5 Mounting location Indoors (weather-protected) Temperature, general -5...< 55 °C Humidity (non-condensing) 5...95 % r.h. Transportation 4) IEC 60721-3-2 Climatic conditions Class 2K3 Temperature -25...70 °C Humidity < 95% r.h. Storage IEC 60721-3-1 Climatic conditions Class 1K3 Temperature -15...55 °C Humidity 5...95 % r.h. Max.
Accessories 6) Potentiometer ASZ7.5 Auxiliary switch ASC10.51 0...1000 Ω ± 5 % Voltage DC 10 V Current rating <4 mA Switching capacity AC 24…230 V, 6 (2) A, potential free External fusing of supply line US installation, UL & cUL ● Non-renewable fuse 6...10 A slow ● Circuit break max. 13 A, tripping characteristic B, C, D to EN 60898 ● Power source with current limitation of max.
SAX61P.. Accessories B and / or A SAX61P03 1 x ASC10.51 1 x ASC10.51 SAX61P03/MO SAX81P03 Accessories B and / or A 1 x ASC10.51 1 x ASC10.51 or 1 x ASZ7.5/..
Connection terminals SAX31P03 AC 230 V 3-position System neutral (SN) Positioning signal (actuator’s stem extends) Positioning signal (actuator’s stem retracts) SAX61P03 AC / DC 24 V D 0...10 V 4...20 mA 0...1000 System neutral (SN) System potential (SP) Positioning signal for DC 0...10 V / 4...
Connection diagrams SAX31P03 A Actuator L Phase N Neutral N1 Controller Y1, Y2 Positioning signals SAX61P03 A Actuator F2 Frost protection thermostat: terminals: 1 – 2 frost hazard / sensor is interrupted (thermostat closes with frost) 1 – 3 normal operation Siemens Smart Infrastructure F3 Thermal reset limit thermostat F4 Frost protection monitor with 0…1000 Ω signal output, does NOT support QAF21.. or QAQ61..
SAX61P03/MO A Actuator N1 Controller G System potential AC/DC 24 V G0 System zero REF Reference line (Modbus RTU) + Bus + (Modbus RTU) - Bus - (Modbus RTU) SAX81P03 16 Siemens Smart Infrastructure A Actuator N1 Controller SN System zero SP System potential Y1, Y2 Positioning signals CE1N4509en 2020-11-26
Dimensions Actuator Type A B C C1 C2 D E [mm] SAX..P.. SAX61P03/MO With ASK39.1 1) Siemens Smart Infrastructure 1) 242 124 150 68 82 267 154 300 200 100 [kg] 80 100 100 - 200 1.780 1.930 2.
External Modbus converter Dimensions in mm Type X SAX61P03/MO 1) [mm] [kg] 250 0.15 1) Included in total weight. Revision numbers Type Valid from rev. no. SAX31P03 ..H SAX61P03 ..I SAX61P03/MO ..B SAX81P03 ..I Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.