Basic Documentation

65 / 87
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Smart Infrastructure Functions and control 2020-01-30
Parameters
259 Op mode R 1 = POS
-
260 MinPosition R 0…100% = 0…10000 0%
261 MaxPosition R 0…100% = 0…10000 100%
262 Actuator runtime R 30s 30s
263 Positioning signal
characteristic
between Y and U
R 0 = Linear (e.g. SAX61../MO + V_G41)
1 = Logarithmic (e.g. SAS61../MO + V_G44)
-
264 Tolerance blockade
monitoring
R 0…100% = 0…10000 4%
513 Backup mode RW 0 = Move to backup position
1 = Maintain last position / 2 = Disabled
2 = Disabled
514 Backup position RW 0…100% = 0…10000 0%
515 Backup timeout RW 60…900s 900s
516 Startup setpoint RW 0…100% = 0…10000 0%
764 Modbus address RW 1…248 / 255 = “unassigned” 255 = “unassigned”
765 Baud rate RW 0 = auto / 1 = 9600 / 2 = 19200 / 3 = 38400 /
4 = 57600 / 5 = 76800 / 6 = 115200
0
766 Transmission
format
RW 0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2 0
767 Bus termination RW 0 = Off / 1 = On
120 Ω electronically switchable
0
768 Bus config.
command
RW 0 = Ready / 1 = Load / 2 = Reject 0
769 Status R See “Function description”, section, “Register
769 “Status”“, page 68
-
Reg. Name R/W Value Example
Device information
1281 Factory Index R Two bytes, each coding
an ASCII char.
5A 00 à “Z” 00
Device is of Series “Z”
1282 Factory Date HWord R Two bytes, the lower
coding the Year (hex)
Read 1282 à 000F
Read 1283 à 0418
HWord LWord
-- YY MM DD
Hex 00 0F 04 18
Dec 00 15 04 24
à Device was manufactured
24 April, 2015
1283 Factory Date LWord R High byte: coding the
month (hex)
Low byte: coding the day
(hex)
1284 Factory SeqNo HWord R Hword + LWord = HEX-
representation of
Sequence number:
Read 1284 à 000A
Read 1285 à A206
AA206(hex) à 696838 (dec)
à Device has sequence
number 696838
1285 Factory SeqNo LWord R
1409 ASN [Char_16..15] R Each register: Two bytes,
each coding an ASCII
char.
ASN is coded beginning
with reg. 1409
Example:
0x47 44 = GD
0x42 31 = B1
0x38 31 = 81
0x2E 31 = .1
0x45 2F = E/
0x4D 4F= MO
à ASN is GDB181.1E/MO
1410
ASN [Char_14..13]
R
1411
ASN [Char_12..11]
R
1412
ASN [Char_10..9]
R
1413 ASN [Char_8..7] R
1414
ASN [Char_6..5]
R
1415 ASN [Char_4..3] R
Reserve
1416 ASN [Char_2..1] R