Basic Documentation

43 / 87
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Smart Infrastructure Handling 2020-01-30
3.2 Commissioning and operation
3.2.1 Function check and Calibration
Before making the function check, the following preconditions must be satisfied:
· Environmental conditions specified in chapter "Technical data" (page 73)
· Actuator is mechanically connected to a Siemens valve
· Actuator is in "Manual operation" mode (page 69).
The actuator can be operated with the help of the "Manual adjuster" (see page 69).
Manual adjuster
Stroke
actuator
Rotary actuator
Control path
valve AàAB
Bypass valve
B à AB
Turning in clockwise
direction
Actuator’s
stem
extends
Actuator’s spindle turns in
clockwise direction
Opening Closing
Turning in counter-
clockwise direction
Actuator’s
stem retracts
Actuator’s spindle turns in
counterclockwise direction
Closing Opening
· Ensure that the actuator’s and valve’s stem, or actuator’s and valve’s spindle are
securely connected in all positions.
· If the actuator is forced to travel beyond its end positions, overload protection
responds.
· Observe information given in chapter "Acting direction and flow characteristic"
on page 57.
Before making the function check, the following preconditions must be satisfied:
· Environmental conditions specified in chapter "Technical data" (page 73).
· Actuator is mechanically connected to a Siemens valve.
· Actuator is in "Automatic" mode (page 69).
Actuator and, if required, accessories are correctly fitted and connected. Also refer
to "Connection Terminals” (page 77)
· Power is applied.
Calibration is required with modulating actuators and SA..61.. before the function
check.
Before making the calibration, the following preconditions must be satisfied:
· A description of the calibration function is given in chapter "Calibration" (page 59
for non-Modbus actuators, page 63 for Modbus actuators).
· Housing cover is removed (step 6 "Special notes on mounting", page 35).
1
Bridge contact
2
Check LED (page 70)
If required, calibration can be repeated any number of times.
4
0
4
0
J
4
0
Mechanically
Notes
Electrically
SA..61..
General notes on