User Manual
9
Optimum start control
Heating
Synco RMH760
Achieve Comfort or Precomfort setpoint at the start of use (per time
switch).
– Precise reaching of the desired temperature conditions.
– Prevent user interventions that waste energy.
The heating circuit is switched on at an earlier time. The main
parameters are the outside air and room temperatures (measured or
calculated). 2 cases:
• Room temperature sensor available: Controller learns the heat up
time per Kelvin room temperature.
• Room temperature sensor not available: Controller uses a room
model to calculate the room temperature; manual entries required.
Applies only when no room temperature sensor is available:
– Optimization mode is set to "With room model".
– Building time constant is entered.
– Room temperature rise is entered.
Function is disabled as factory setting by setting the maximum
forward shift to 0 hours.
Enable function by entering a value > 0 hours.
Main menu > Settings > Heating circuit 1…3 > Optimizations/influences
Operating line Recommendation
Forward shift on max 6 hour
Further information
Topic Doc. Sec. Comment/Recommendation
Optimum start control P3133 9.7.2 Principles and additional details
Room model P3133 9.7.1
Building time constant P3133 9.5.1 Maintained at factory setting 20 hours:
– Light construction: 10 hours
– Medium construction: 20 hours
– Heavy construction: 50 hours
Room temperature rise P3133 9.7.2 Maintained at factory setting of 60 min/K
Plant
Controller
Target
Savings potential
Description
Prerequisites
Enable function