User Manual

9
Optimum start control
Heating
Synco RMH760
Achieve Comfort or Precomfort setpoint at the start of use (per time
switch).
Precise reaching of the desired temperature conditions.
Prevent user interventions that waste energy.
The heating circuit is switched on at an earlier time. The main
parameters are the outside air and room temperatures (measured or
calculated). 2 cases:
Room temperature sensor available: Controller learns the heat up
time per Kelvin room temperature.
Room temperature sensor not available: Controller uses a room
model to calculate the room temperature; manual entries required.
Applies only when no room temperature sensor is available:
Optimization mode is set to "With room model".
Building time constant is entered.
Room temperature rise is entered.
Function is disabled as factory setting by setting the maximum
forward shift to 0 hours.
Enable function by entering a value > 0 hours.
Main menu > Settings > Heating circuit 1…3 > Optimizations/influences
Operating line Recommendation
Forward shift on max 6 hour
Further information
Topic Doc. Sec. Comment/Recommendation
Optimum start control P3133 9.7.2 Principles and additional details
Room model P3133 9.7.1
Building time constant P3133 9.5.1 Maintained at factory setting 20 hours:
Light construction: 10 hours
Medium construction: 20 hours
Heavy construction: 50 hours
Room temperature rise P3133 9.7.2 Maintained at factory setting of 60 min/K
Plant
Controller
Target
Savings potential
Description
Prerequisites
Enable function