Max. economy changeover of heat recovery
M
Xx [EAT]
Ventilation
Synco RMU7x0
Optimized heat recovery saves heat and cooling energy (using a
maximum economy changeover).
Optimum control of heat recovery with regard to operating costs.
Principle: Comparative measurements between outside air and
room/extract air temperature.
The output for the heat recovery equipment is inverted, if the set
MECH limit value is exceeded.
Acts on heating as well as cooling sequences.
Heat recovery equipment is available.
Outside air and room/extract air temperature sensors are available
on the controller.
Main menu > Settings > Aggregates > Heat recovery equipment
Operating line Recommendation
MECH limit value 3.0 K
Further information
Topic Doc. Sec. Comments
Heat recovery equipment P3150 10.4 Principles and additional details
Changeover options P3150 10.4.3 With external signal
With set value
Based on an adjustable difference
(the example here)
Plant
Controller
Target
Savings potential
Description
Prerequisites
Enable function