User Manual

15
Interval operation circulation pump
Heating
Synco RMH760
Circulation pumps are operated at intervals (1/3 of the time) only.
This saves electricity for the pump and is sufficient to maintain hot
water supply.
Savings of 2/3 of the electricity for circulation pump versus
standard operations.
During interval operation, the circulation pump operates on the hour
and half hour for 10 minutes each time, in other words, with
interruptions of 20 minutes. The pump only operates when enabled
per time switch or parameterization. At the start of an enable the
pump always operates for 10 minutes; regardless of the time.
None
Function is enabled as factory setting.
Main menu > Settings > DHW > DHW
Operating line Factory setting
Interval operation circ pump Yes
Further information
Topic Doc. Sec. Comment/Recommendation
Interval operation circulation pump P3133 10.11.3 Principles and additional details
Circulating pump time switch P3133 5.1.2 Principles and additional details
Plant
Controller
Target
Savings potential
Description
Prerequisites
Enable function