Set mixing controller
Heating
Synco RMH760
High level of control accuracy achieved by setting the mixing heating
circuit in an optimum manner.
An optimally set mixing valve achieves the desired temperature in
an energy-efficient manner.
The actuator runtime must be adjusted to the actual actuators. The
setting is important for both 3-point actuators as well as for DC
0…10 V actuators.
For 3-point actuators, the set time should be higher when in doubt,
since the actuator does not operate optimally in the range from 0 %
or 100 % open.
None
In addition to P-band Xp and integral action time Tn, it is, above all,
the actuator runtime that needs to be adapted or checked.
Main menu > Settings > Heating circuit 1…3 > Mixing circuit controller
Operating line Recommendation
Actuator running time Positioning time actuator:
Per actuator type label
From the actuator datasheet
Stop using time
Further information
Topic Doc. Sec. Comment/Recommendation
Mixing valve control P3133 5.7.2 Principles and additional details