Set mixing controller
Heating
Synco RMH760
High level of control accuracy achieved by setting the mixing heating
circuit in an optimum manner.
– An optimally set mixing valve achieves the desired temperature in
an energy-efficient manner.
The actuator runtime must be adjusted to the actual actuators. The
setting is important for both 3-point actuators as well as for DC
0…10 V actuators.
For 3-point actuators, the set time should be higher when in doubt,
since the actuator does not operate optimally in the range from 0 %
or 100 % open.
None
In addition to P-band Xp and integral action time Tn, it is, above all,
the actuator runtime that needs to be adapted or checked.
Main menu > Settings > Heating circuit 1…3 > Mixing circuit controller
Operating line Recommendation
Actuator running time Positioning time actuator:
• Per actuator type label
• From the actuator datasheet
• Stop using time