Optimum stop control
Heating
Synco RMH760
Achieve Economy or Protection mode setpoint at the end of use (per
time switch).
– Precisely accurate achievement of the desired temperature
conditions.
– Prevent user interventions that waste energy.
The heating circuit is switched off at an earlier time. Main
parameters are outside air and room temperatures.
– A room temperature sensor is available.
– Optimization mode is set to "With room temperature sensor".
Function is disabled as factory setting by setting the maximum early
shutdown to 00:00 h.min.
Enable function with a value > 00:00 h.min.
Main menu > Settings > Heating circuit 1…3 > Optimizations/influences
Operating line Recommendation
Early shutdown max 01:00 h.min
Further information
Topic Doc. Sec. Comment/Recommendation
Optimum stop control P3133 9.7.2 Principles and additional details
Type of optimization P3133 9.7.1 Must be set to "With room temperature sensor”
Plant
Controller
Target
Savings potential
Description
Prerequisites
Enable function