User Manual
Guide – From energy consumer to energy
user
Energy-conscious behavior starts with selecting the right product (Synco
controllers). Your Synco controller reliably and accurately ensures optimum comfort
at minimum consumption.
Operator units (room units, thermostat valves) and building operations allow you to
further decrease energy consumption (see measures below).
Siemens wishes you much success with saving energy!
Properly run heating, ventilation, and air
conditioning plants
Presettings
The following room temperature setpoints for residential and working areas are set
optimally on the heating and ventilation controllers:
Symbol Room operating
mode
Reference value for
heating
Reference value for
cooling
Comfort 21 °C 24 °C
Precomfort 19 °C 28 °C
Economy 15…16 °C 30 °C
Note on room operating modes:
Comfort
Setpoint for an occupied room.
It ensures a comfortable room climate.
Precomfort Energy saving setpoint for the room to quickly achieve
Comfort levels when switching to Comfort mode.
Economy Plant Off. Only minimum or maximum room
temperature is guaranteed for the room (sustained
mode).
Protection Plant Off. Frost protection active.
Contact your installer to adjust setpoints and scheduler programs of your heating or
ventilation controller in the event of major, lasting changes to building occupancy
and/or building occupancy hours.
6