Installation Instructions

Document No. 129-611
Installation Instructions
January 19, 2016
Page 2 of 3 Siemens Industry, Inc.
Wiring
All wiring must conform to NEC and local codes and
regulations
Use earth ground isolating, step-down Class 2 transformers.
Do not use auto transformers.
Determine supply transformer rating by adding up the total VA
of all actuators used.
The maximum rating for Class 2 step-down transformers is
100 VA
Do not power more than 10 actuators with one transformer.
(Use 0.5 amp fuse on secondary actuator.)
1. Remove actuator cover screws using either a No. 2
Phillips or a No. 2 flat-blade screwdriver and detach
actuator cover.
2. Access terminal block and attach wires per Figure 2
through Figure 5.
3. Replace actuator cover. Use cover screws to secure
actuator cover in place.
Terminals G and G0 must be properly wired for
correct function and full life of the actuator.
If the actuator makes a buzzing noise upon
reaching setpoint, G and G0 are improperly
wired and should be reversed.
G
Hot (+)
Y1
Connected to Neutral (-) extends actuator stem
Y2
Connected to Neutral (-) retracts actuator stem
Figure 2. SAS81.03U 24 Vac NSR Floating Control
Neutral Switch.
G
Neutral (-)
Y1
Connected to Hot (+) extends actuator stem
Y2
Connected to Hot (+) retracts actuator stem
Figure 3. SAS81.03U 24 Vac or 24 Vdc NSR Floating
Control Hot Switch.
G
Hot (+)
G0
Neutral (-)
Y1
Connected to Neutral (-) extends actuator stem
Y2
Connected to Neutral (-) retracts actuator stem
Figure 4. SAS81.33U 24 Vac SR Floating
Control Neutral Switch.
G
Hot (+)
G0
Neutral (-)
Y1
Connected to Hot (+) extends actuator stem
Y2
Connected to Hot (+) retracts actuator stem
Figure 5. SAS81.33U 24 Vac or 24 Vdc SR Floating
Control Hot Switch.
Start-Up
The valve body (normally open or normally closed) determines
action of the complete valve/actuator assembly.
Troubleshooting
Check wiring for proper connections and secure
attachments.
Check for adequate power supply.
References
Powermite 599 MT Series SAS Electronic Valve Actuator,
24 Vac or 24 Vdc, Floating Control (3-Position) Technical
Instructions (155-681).