Brochure
6 / 12
Siemens CE1N4581en
Building Technologies 2015-05-19
Forced control
Positioning signal Z SAS61.. R = 0…1000 Ω, G, G0
R = 0…1000 Ω stroke proportional to R
Z connected to G max. stroke 100 %
Z connected to G0 min. stroke 0 %
Voltage max. AC 24 V +20 % /
max. DC 24 V +20 % / -15 %
Current draw ≤ 0.1 mA
Position feedback
U SAS61.. DC 0…10 V ± 1 %
Load impedance > 10 kΩ res.
Load max. 1 mA
Connecting cable
Wire cross-sectional areas 0.75…1.5 mm
2
, AWG 20…16
1)
Cable entries SAS.. (EU) 1 entry Ø 16.4 mm (for M16)
1 entry Ø 20.5 mm (for M20)
SAS..U (US) 2 entries Ø 21.5 mm for ½“ tube
connection
Degree of protection
Housing protection (Mounting position) IP 54 as per EN 60529
2)
(vertical)
Insulation class As per EN 60730
Actuators SAS31.. AC 230 V II
Actuators SAS61.. AC / DC 24 V III
Actuators SAS81.. AC / DC 24 V III
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Indoors, outdoors
3)
Temperature general -5…55 °C
Humidity (noncondensing) 5…95 % r. F.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -25…70 °C
Humidity <95 % r. F.
Storage IEC 60721-3-1
Temperature -15…55 °C
Humidity 5…95 % r. F.
Directives and Standards
Product standard EN60730-x
Electromagnetic compatibility (Application) For residential, commercial and industrial
environments
EU Conformity (CE) CE1T4581xx
4)
RCM Conformity CE1T4581en_C1
4)
UL, cUL AC / DC 24 V UL 873 http://ul.com/database