ACVATIX TM Electromotive actuators for valves SAS.. Electromotive actuators with 5.5 mm stroke and 400 N positioning force ● ● ● ● ● ● ● CE1N4581en 2020-07-09 SAS31.. Operating voltage AC 230 V, 3-position control signal SAS61.. Operating voltage AC 24 V / DC 24 V, positioning signal DC 0...10 V / DC 4...20 mA / 0...1000 Ω SAS61../MO operating voltage AC 24 V / DC 24 V, RS-485 for Modbus RTU communication SAS81..
Application To operate Siemens 2-port and 3-port valves: ● Types V..G44.., VVG55.., and VVG549.. ● 5.5 mm stroke Used as control and shutoff valves in heating and ventilation plants. Together with the ASK30 mounting kit, all former Landis & Gyr valves with 4 mm or 5.5 mm stroke can also be operated: X3i.., VVG45.., VXG45.., VXG46.., VVI51... Functions Function Description 3-position control A 3-position signal controls the actuator via connection terminals Y1 or Y2.
Types Type Item no. Operating voltage SAS31.00 S55158-A106 SAS31.03 S55158-A107 SAS31.50 S55158-A108 SAS31.53 S55158-A109 SAS61.03 S55158-A100 SAS61.03U S55158-A100-A100 SAS61.03/MO S55158-A121 SAS61.33 S55158-A101 SAS61.33U S55158-A101-A100 SAS61.33/MO S55158-A122 Control signal Power Pos. consumption time 2.8 / 2.4 VA 6) 120 s AC 230 V 3.5 / 2.9 VA 6) 3-position 5.5 / 3.8 VA 6) 30 s Spring return Func.
Ordering (example) Type Stock number SAS31.00 S55158-A106 Designation Number of pieces Actuator 1 + auxiliary components such as connections, aux switches, etc. Spare parts Description S55845-Z180 Type ASQ1: Housing cover with associated screws and light guide as component, without laser labeling 4041Z06 Stock number Compatibility Valves PN16 VVG44.. (2-port) Actuators SAS.. VXG44.. (3-port) DN Medium: 1…120 °C G kvs ∆ps ∆pmax 3 [inch] [m /h] [kPa] [kPa] VVG44.15-..1) VXG44.15-..
Valves PN25 VVG55.. (2-port) Actuators SAS.. 1) DN Medium: 1…130 °C G kvs 3 ∆ps ∆pmax [inch] [m / h] [kPa] [kPa] VVG55.15-..2) 15 G¾B 0,25 / 0,4 / 0,63 2500 1200 2) VVG55.15-.. 15 G¾B 1 / 1,6 / 2,5 2000 1200 VVG55.20-4 20 G1B 4 1000 1000 VVG55.25-6.3 25 G1¼B 6,3 800 800 1) VVG55 is replaced by VVG549 from Jan 1, 2017. 2) = use kvs value Product documentation Title Content Document ID Actuators SAS.., SAT..
Engineering SAS31.. and SAS81.. 3-position actuators must have their own specific controller, see "Conenction Diagrams". SAS61.. Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA. Modulating actuators have an input impedance of 100 kΩ. SAS61../MO The Modbus converter is dimensioned for analog control at 0…10 V. Note: Keep the analog signal setting on the actuator as is (switch 1 to Off); adjustment not possible.
Disposal WARNING Tensioned return spring Opening the actuator housing can release the tensioned return spring resulting in flying parts that may cause injury. ● Do not open the actuator body. The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage. · Dispose of the device through channels provided for this purpose. · Comply with all local and currently applicable laws and regulations.
Technical data Power supply Operating voltage SAS31.. AC 230 V ± 15% SAS61.. AC 24 V ± 20% / DC 24 V +20% / -15% or AC 24 V class 2 (US) SAS81.. AC/DC 24 V ± 20 % or AC 24 V class 2 (US) Frequency 45…65 Hz External supply line fusing (EU) Fuse slow 6 A…10 A or fuse switch max. 13 A, release characteristic B,C,D as per EN 60898 power source with current limitation of max. 10 A Power consumption At 50 Hz See "Type summary"; stem retracts/extends Typical inrush current 1) SAS31.. 2.
Parallel connection SAS61.. ≤ 10 (depending on controller output) Forced control Z positioning signal SAS61.. R = 0…1000 Ω, G, G0 R = 0…1000 Ω Stroke proportional to R Z connected to G Max. stroke 100% Z connected to G0 Min. stroke 0% Voltage Max. AC 24 V ±20% / Max. DC 24 V +20% / -15% Current draw ≤ 0.1 mA Voltage range SAS61.. DC 0...10 V Load impedance > 10 kΩ resistive Load Max. 1 mA Position feedback U Connection cables 0.75…1.
Standards Product standard EN60730-x Electromagnetic compatibility (field of use) For residential, commercial and industrial environment EU conformity (CE) CE1T4581xx 4) (8000073402) CE1T4581en_C1 4) RCM conformity (8000069574) UL, cUL UL 873 http://ul.
Diagrams Internal diagrams SAS31.5.. SAS31.0.. Accessories, plug A 1x ASC10.51 ASC10.51 AC 230 V AC 230 V M M SAS61.. Accessories, plug A 1x ASC10.51 ASC10.51 SAS61../MO AC 24 V / DC 24 V 1 6 8 G REF + 9 US installation, UL & cUL 100% A6V10137201_G01 M 0% G0 AC 24 V class 2 5 A gen. purp. 2 SAS81.0.. SAS81.33, SAS81.
Connection terminals SAS31.0.. AC 230 V, 3-position Sytem neutral (SN) Positioning signal (actuator’s stem extends) Positioning signal (actuator’s stem retracts) SAS31.5.. AC 230 V, 3-position Sytem neutral (SN) Y1 Positioning signal (actuator’s stem extends) Positioning signal (actuator’s stem retracts) Fail-safe function SAS61..
Electrical accessories ASC10.51 Auxiliary switch, adjustable switching positions, AC 24…230 V Sytem potential (SP) Closes (actuator stem extends) Opens (actuator stem extends) Connection diagrams SAS31.0.. SAS31.5.. AC 230 V L L Y2 Y1 N N1 N SAS61..
SAS61.33 / SAS61.33U / SAS61.53 AC/DC 24 V SP F1 G 1 3 M G 2 F2 1 3 2 F3 R M F4 N1 U M Z SN SAS61../MO RS485 B G0 G REF G0 + A - REF G A6V10137201_A01 AC/DC 24 V N1 - + A SAS81.0..
SAS81.33, SAS81.33U AC/DC 24 V SP G F1 Y1 Y2 G0 N1 SN A Actuator REF Reference line (Modbus RTU) F1 Temperature limiter SN System zero F2 Frost protection thermostat; terminals: SP System potential AC/DC 24 V 1 – 2 Frost hazard / sensor is Off (thermostat closes upon frost) 1 – 3 normal operation Siemens Smart Infrastructure F3 Thermal reset limit thermostat U Position feedback F4 Frost protection monitor with 0…1000 Ω signal output, Y does NOT support QAF21.. or QAF61..
Dimensions Actuators SAS.. with manual adjustment Type SAS.. SAS../MO 2) With ASK39.2 A B C C1 C2 D E F [mm] [mm] [mm] [mm] [mm] [mm] [mm] [inch] [mm] [mm] [kg] 1 151 80 93 21,9 71.1 29,9 21,8 G¾ 100 200 0,55 155 126 248 99 149 2 0,4 M16 1) M20 1) 3) 3) 1 2 0,55 1) SAS..U: ½“ (dia. 21.5 mm) 2) Device has fixed connection cable - cable entry 2 occupied 3) Thread length max. 9 mm Actuators SAS.. without manual adjustment Type SAS..
External Modbus converter Type SAS..
Revision numbers Type Valid from rev. no. SAS31.00 ..B SAS31.03 ..B SAS31.50 ..B SAS31.53 ..B SAS61.03 ..B SAS61.03U ..B SAS61.03/MO ..B SAS61.33 ..B SAS61.33U ..B SAS61.33/MO ..A SAS61.53 ..B SAS81.00 ..B SAS81.03 ..B SAS81.03U ..B SAS81.33 ..B SAS81.33U ..B Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 18www.siemens.