Modbus registers
Reg. Name R/W Range/Listing Factory setting
Process values
1 Setpoint RW 0...100 % = 0...10000
-
2 Forced control RW 0 = Off / 1 = Extend / 2 = Retract / 3 = Stop
3 Actual Value. R 0...100 % = 0...10000
256 Command RW 0 = Ready or calibrating /
1 = Not available / 2 = Self-test /
3 = Reinitialize / 4 = Remote reset
Parameter
259 Control mode R 1 = POS -
260 MinPosition R 0...100 % = 0...10000 0 %
261 MaxPosition R 0...100 % = 0...10000 100 %
262 Actuator runtime R 30 30 s
263 Positioning signal
curve between Y and U
R 0 = Linear (e.g. SAX61../MO + V..G41..)
1 = Logarithmic (e.g. SAS61../MO + V..G44..)
-
264 Tolerance blockade
monitoring
R 0...100 % = 0...10000 4 %
513 Backup mode
(replacement mode)
RW 0 = Go to backup position / 1 = Not available / 2 =
Deactivated
2 = Deactivated
514 Backup position RW 0...100 % = 0...10000 0 %
515 Backup timeout RW 0...65535 900 [s]
516 Start-up setpoint RW 0...100 % = 0...10000 0 %
764 Modbus address RW 1...248 / 255 = "Unassigned" 255 = "Unassigned"
765 Baud rate RW 0 = Auto / 1 = 9600 / 2 = 19200 / 3 = 38400 / 4 =
57600 / 5 = 76800 / 6 = 115200
0
766 Transmission format RW 0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2 0
767 Bus termination RW 0 = Off / 1 = On
120 Ω electronically switchable
0
768 Bus conf. command RW 0 = Ready / 1 = Load / 2 = Discard 0
769 Status R See Register 769 "State" [ 8] -
Device information
1281 Index R
Basic documentation
CE1P4040; CE1P4041
1)
1282-83 Manufacturing date R
1284-85 Serial number R
1292 Actuator type R
1409-16 ASN [characters 16..1] R