User Manual

4
Siemens A6V101037195_en--_b
Smart Infrastructure 2020-07-09
User interface
Pushbutton operation
Action Pushbutton operation Feedback message
Current Modbus address
(starting from lowest address
position)
Button press <1 s 1st digit (single digit): red
10-digit (double digit): green
100-digit (triple digit): orange
The LED blinks 1 x blue after the
address indication if bus termination
is switched on
Example:
124 = 4 x red, 2 x green, 1 x orange
Switch on/off bus termination
Switch-on Press the button 3 times Blinking or flashing of LED stops
(termination mode).
Briefly press the button 1 x Blue LED flashes 1 x.
Press button until the LED turns red RED LED is lit (confirmation).
Release button LED not lit.
Address is indicated.
LED blinks 1 x blue after the address
indication
Device enters normal mode.
Switch off Press the button 3 times Blinking or flashing of LED stops
(termination mode).
Briefly press the button 1 x RED LED is lit (confirmation).
Release button Device enters normal mode.
Enter Modbus address using
pushbutton
Button press >1 s and <5 s See Enter address using pushbutton
[ 5]
Enable pushbutton addressing
(together with Climatix
TM
controllers)
Button press >5 s and <10 s Red LED is lit and goes off after 5 s.
Release button Orange LED lit.
Reset to factory settings Button press >10 s LED flashes orange.
LED colors and flashing patterns
Color Blinking pattern Description
Green 1 s on / 5 s off Normal mode without bus traffic
Flickering Normal mode with bus traffic
Orange / green 1 s orange / 1 s green Device is in override control mode
Orange 1 s on / 1 s off Bus parameter not yet configured
1 s on / 5 s off Device is in backup mode (replacement
mode)
Red Permanently lit Mechanical error, device blocked, manual
intervention or calibration
1 s on / 5 s off Internal error
0.1 s on / 1 s off Invalid configuration, e.g. Min = Max
Blue Flickers 1 x after indicating the address Bus termination active