User Manual
7 / 14
Siemens RXL24.1 – Room controller CM2N3878en_07
Building Technologies 2015-12-23
Mounting instructions
The room controllers can be mounted in any orientation, and fixed as follows:
3873J06
3873J07
Rail mounting
The housing base is designed for snap-
mounting on DIN rails, type EN50022-35 x
7.5 (can be released with a screwdriver).
Surface mounting
There are two drill holes for screw-mounting (see “Dimensions”
for drilling template). The housing base is fitted with raised
supports.
Screws: Max. diameter 3.5 mm, min. length 38 mm
STOP
Note!
Tightening torque for fixing screws max. 1.5 Nm
When mounting note the following:
• The controller should not be freely accessible after mounting. It must be
mounted in a cabinet or behind a cover that can only be opened / removed with
a key or a tool.
• Ensure adequate air circulation to dissipate
heat generated during operation.
• Easy access is required for service personnel
• Local installation regulations must be observed.
Mounting instructions and a drilling template are printed on the controller
packaging.
Commissioning
The RXL24.1 room controller is commissioned with one of the following tools:
− Synco ACS via the OCI700 interface
− "HandyTool" via PPS2.
The definitive application and the controller's location are handwritten in the
labeling fields "Appl." and "Loc" in the commissioning stage.
A special test mode (HandyTool) is available for operation of the outputs and
interrogation of the inputs.
Labeling
Function test