Siemens RXL24.1 Room controller CM2N3878en_07
Building Technologies 2015-12-23
Connection terminals
CP –
CP +
CE
CE +
3878A08
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M
D1
GND
D2
Y1
G
Y2
B1
Bus
12 4 3
QAX...
T
M
AC 24 V
SELV / PELV
Y3
G
Y4
M
19 19
21
G0
G
G0
21
G
CE
CE +
N.C.
Measured value input
B1
1
Measured value input for LG-Ni 1000 sensors
M
2
Measured value input ground
Signal inputs
D1
4
Signal input
GND
5
Signal ground
D2
6
Signal input
Triac outputs
Y1
7
AC 24 V, 0.5 A switching output
G
8
AC 24 V actuator supply
Y2
9
AC 24 V, 0.5 A switching output
Y3
10
AC 24 V, 0.5 A switching output
G
11
AC 24 V actuator supply
Y4
12
AC 24 V, 0.5 A switching output
Room unit
CP
13
PPS2 ground
CP+
14
PPS2 data
CE+
15
Bus
CE
16
Bus
Bus (plug-in connection)
CE+
17
Bus
CE
18
Bus
Power supply
G0
19
Controller ground
G
21
AC 24 V +/- 20 %
Local installation regulations must be observed.
Proprietary RJ45-type tool socket
1
3206Z01
2 3 4 5
6 7 8
1 Bus (CE+)
2 Bus (CE–)
3 Not used
4 Not used
5 +12VDC
6 RxD
7 PPS2 (CP+) / TxD
8 PPS2 (CP)
RXL24.1
Caution
Tool socket