User Manual
3/16
Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09
Building Technologies 2015-12-23
Applications
The following applications are available for the RXL2… room controllers:
Application group (type)
Fan-coil applications
FC-10
(with RXL21.1)
FNC02 2-pipe system with changeover
FNC04 4-pipe system
FNC08 4-pipe system and
room/supply air cascade control
FNC20 4-pipe system
with single damper control
FC-11
(with RXL21.1)
FNC10 2-pipe system with changeover and
outside air damper
FNC12 4-pipe system with outside air damper
FNC18 2-pipe system with changeover and
radiator
FC-12
(with RXL22.1)
FNC03 2-pipe system with changeover and
electric re-heater
FNC05 4-pipe system with electric re-heater
Only one application at a time can be activated with the tool (Synco ACS or
"HandyTool").
Types
The RXL21.1 and RXL22.1 room controllers differ only in the number of outputs
available:
Type AC 24 V triac outputs Relay outputs
RXL21.1
For 2 thermic valve actuators or
two 3-position actuators
For 3-speed fan control
RXL22.1
For 2 thermic valve actuators or
one 3-position actuator
For 3-speed fan control;
internal relay for electric heating
coil
RXZ20.1
Accessories: Terminal covers
Ordering
When ordering please specify the quantity, product name, type code and application
group.
30 Room controllers, type RXL21.1/FC-10
Note
Example: