User Manual

13/16
Siemens RXL21.1, RXL22.1 Room controllers CM2N3877en_09
Building Technologies 2015-12-23
Connection diagrams Connection of field devices, room unit, bus and power supply
1
2
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
M
D1
GND
D2
Y1
G
Y2
CP –
CP +
B1
Y3
G
Y4
19
19
21
G0
G
G0
25
26
27
28
Q13
Q14
Q24
Q34
AC 24 V
Bus
B2
PPS2
Bus
N1
21
G
CE –
CE +
CE –
CE +
1
2
4
3
1
2
4
5
6
7
8
9
13
14
15
16
17
18
M
D1
GND
D2
Y1
G
Y2
CP –
CP +
B1
19
19
21
G0
G
G0
25
26
27
28
Q13
Q14
Q24
Q34
AC 24 V
Bus
B2
PPS2
Bus
N2
3877A11_01
Q43
Q44
23
22
24
21
G
CE –
CE +
CE –
CE +
N.C.
1
2
4
3
Y3
Y3.1
Y1.2
M
Y3.2
M
Y1
Y2
GL
Y1.1
M
GL
M
Y4
2
3
1
N
L
1
N
L
Q1
Q1.1
Y1
Y2
GL
Y1.1
M
Y1.2
M
Y2.2
M
D1
D2
T
B1
2
3
1
N
L
1
N
L
Q1
Q1.1
L
N
Q2
D1
D2
T
B1
N1 / N2 RXL21.1 / RXL22.1
B1 LG-Ni 1000 temperature sensor
D1, D2 Volt-free contacts (window contact, occupancy sensor, etc.)
Y1...Y4 AC 24 V thermic valve actuators
Y1.1, Y3.1 Motorized AC 24 V, 3-position valve or damper actuator
Y1.2, Y2.2, Y3.2 Electromechanic AC 24 V, 2-position valve actuator
B2 QAXroom unit
Q1 3-speed fan
Q1.1 1-speed fan
Q2 Electric heating coil
Twisted pair
Fans connected to relay outputs Q14 … Q34 must not be operated in
parallel. For parallel operation use cut-off relays or slave room controllers.
At Q2 (1.8 kW max. resistive load), use additional external fuses of max. 10 A
to protect the pcb tracks.
For information on the compatibility of field devices with the RXL21.1 and RXL22.1
room controller, refer to the various application descriptions (see the FNC description of
functions, document CA110785)
Note