User Manual

6 / 14
Siemens RXC39.5 Room controller CM2N3856en_07
Building Technologies 2015-12-23
The simultaneous load on outputs Y1, Y2 must not exceed 12 VA
The maximum load on each output must not exceed 12 VA
Equipment
Y1, Y2
2 thermic valve actuators, type STP73
6 VA each
Simultaneous load:
2 thermic valve actuators *
6 W (12 W) **
6 W (12 W)
* The heating and cooling sequences are never operative simultaneously.
Therefore only the actuators for one of the two sequences need to be included
when calculating the total load.
** When cold, thermic valve actuators have a consumption of approximately 6 W. A
maximum of two thermic actuators may be connected to any one Y.. output.
The DC 0...10 V control outputs YC...YC4 deliver max. 1.5 mA.
The AC 24 V supply outputs for field devices (G, terminals 5, 27, 29, 33, 37)) may
be charged with a total of max. 12 VA.
Mounting
The room controllers can be mounted in any orientation, and fixed as follows:
80060
80061
Rail mounting
The housing base is designed for snap-
mounting on DIN rails, type EN50022-
35x7.5 (can be released with a screw-
driver)
Surface mounting
There are four drill holes for screw-
mounting (see “Dimensions” for drilling
template). The housing base is fitted with
raised supports.
When mounting note the following:
The controller should not be freely accessible after mounting
Ensure adequate air circulation to dissipate heat generated during operation.
Easy access is required for service personnel
Local installation regulations must be observed.
Mounting instructions and a drilling template are printed on the controller packaging.
AC 24 V triac outputs
Example
DC 0...10 V outputs
AC 24 V supply for