User Manual

8/10
Siemens RXC41 Extension module for the control of blinds CA2N3843en_06
Building Technologies 2015-12-14
80052
G0
ADDRz
ATTNz
VCC
DG
G
RDY
DATA
CLK
DG
G0 Ground
ADDRz Module address
ATTNz Handshake
VCC DC 5 V
DG Electronics ground
G AC 24 V
RDY Handshake
DATA Data
CLK Clock
DG Electronics ground
Connection diagrams
N1 RXC41
D1 ... D4 Volt-free momentary contact switches
Q1, Q2 Electric motors for blinds
F1 Internal fuse T3.15 A (RXC41.1)
F2 External fuse ≤10 A (RXC41.5)
Parallel connection of blind motors to one output must be avoided, as this can
damage the motors.
The maximum load per module (for both motors together) is restricted to 3A.
Connector for
extension modules
STOP
Note!