User Manual
11/14
Building Technologies RXC34.1 – Room controller, basic module CA2N3847en_02
12.01.2007
Relay outputs
Q11
23
N/C contact
Q12
24
N/C contact
Q13
25
N/O contact
Q14
26
N/C contact
Analog inputs / outputs
Y12
27
Analog OUT 0 … 10 V
G0
28
Controller ground
Y13
29
Analog OUT 0 … 10 V
G
30
AC 24 V (phase)
U3
31
Analog IN 0 … 10 V
M
32
Measuring neutral (G0)
G
33
AC 24 V (phase)
U4
34
Analog IN 0 … 10 V
M
35
Measuring neutral (G0)
Signal input for volt-free contacts
D1
36
Signal input
GND
37
Signal input ground
D2
38
Signal input
• Observe the technical data for the relay outputs.
• Local installation regulations must be observed.
Standard RJ45 tool socket for LonWorks® devices.
1
3206Z01
2345678
1 LonWorks®, Data A (CLA)
2 LonWorks®, Data B (CLB)
3 Not used
4 Not used
5 Not used
6 Not used
7 PPS2 (CP+)
8 PPS2 (CP–)
80052
G0
ADDRz
ATTNz
VCC
DG
G
RDY
DATA
CLK
DG
G0 Ground
ADDRz Module address
ATTNz Handshake
VCC DC 5 V
DG Electronics ground
G AC 24 V
RDY Handshake
DATA Data
CLK Clock
DG Electronics ground
STOP
Caution
Tool socket
Connector for
extension modules