User Manual

87/90
Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Commissioning 12.06.2006
Parameters R / W Description
@AO g.EMV
(Specification of parameter
EMV optional)
W Command when g=1 (blinds):
Up (0) / Down(1) / Down(2) / Auto(3)
Command when g=101 (lighting zones):
Off(0) Dimming (1…100%) Auto(255)
1)
@AO g.PARINT(1)
R
Last command issued
2)
@AO g.PARINT(2) R / W
Operating mode: Local (0) / Remote(1)
@AO g.PARINT(3) R Priority (1..100)
@AO g.FBV -
3)
1)
The dimming command presupposes integration of the lighting commands
(not possible with Light Override)
2)
EMV is immediately reset to –1 as soon as the command has been issued.
FBV changes together with EMV. There are no feedback signals for the group as a whole.
The feedback signal must be inspected by the allocated link points.
Read @AOx'y.FBV.
The parameter values for the group commands and operating modes are passed on to
the allocated link points @AOx'y for the blinds and lighting zones. These ensure the
output to the relevant network variable. For details refer to Mapping functions 3.1.26 to
3.1.29.
These are operated directly via the parameters of the link point concerned.
Parameters R / W Description
@AOx'y.EMV W
Command (see above)
@AOx'y.PARINT(1) R
Last command issued
2)
@AOx'y.PARINT(2) R / W Mode (Local, Remote)
@AOx'y.PARINT(4)
Reserved Internal memory.
Must not be used for other purposes
@AOx'y.FBV
R Feedback
@AOx'y.GROUP R Room number
@AOx'y.FICT R 1 (Normal) / 0 (Alarm – not connected)
Note that the next group command will overwrite the last command issued to the
individual blind or lighting zone.
Transfer
Operating the blinds and
lighting zones