Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Commissioning 12.06.2006
5.8 Operating the blind and lighting groups
The RX master makes the group connections for blinds and lighting zones in
accordance with the entries in the GroupConfig.col file (TSK 112).
For more information refer to "Group definition" in the "Engineering" section.
The blinds of controllers 1M55 and 2M56 in Rooms 1 and 2 are to be assigned to a
blind group, and the lighting zones of the same controllers to a lighting group (Priority
level 3 for both groups). The entries in TSK 112 are as follows:
3000 DATA 1,3,55,56,-9
3001 DATA –9
4000 DATA 101,3,55,56,-9
4001 DATA -9
Based on these entries, the CFE software generates the group points @AO1 (blind
group) and @AO101 (lighting group) and connects them to the data points for the
blinds and lighting zones.
Blind 1
Blind 2
LightZone 1
LightZone 2
1 M 55
Blind 1
Blind 2
LightZone 1
LightZone 2
2 M 56
@AO56'1
@AO56'2
@AO56'5
@AO56'6
@AO55'1
@AO55'2
@AO55'5
@AO55'6
@AO 1
@AO 101
The following parameters of the two group points @AOg (g=1 /101) can now be
operated (R: Read / W: Write) :
Introduction
Example
Operating the groups