User Manual

83/90
Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Commissioning 12.06.2006
5.5 General options for operation
The integrated data points can be operated with the VISOTOOL Editor, for example:
To read the effective heating setpoint: @TCR1.ASPH
To specify a new Comfort heating setpoint: @TCR1.SPCH:=20.5
(basic setpoint setting for Comfort/Heating)
Room management reports can be obtained with the command RMR, for example:
RMR for a report on all TEC rooms
RMR @ TCG n for a specific TEC group
RMR @ TCR n for a specific TEC room
The example below shows the command and the room management report for room
TCR74. It will be seen from the report that the room has one RXC controller, TEC No.
39, for which the parameters and values are also shown:
rmr @tcr74
RMR 17:06:05 16-AUG-1999/MO
!FI TCR $d070'TCR74 (T39)
16-AUG-1999 17:04:18 AOPST=0
SOPST=0 APRST=0
SOMOD=0 ASTH =0 VSPA =0
MACT =0 ASTC =0 VEXA =0
MOPST=2 RRSC =0 RWINO=0
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
! TEC ! ARTP !OHWA !OCWA !OXWA !OHAIR!OCAIR!OHHB !OEAIR ! OFAN !AIRVS1!AIRVE !
! ! !OHWA2!OCWA2! ! ! ! ! ! !AIRVS2! !
! ! [C] ! [%] ! [%] ! [%] ! [%] ! [%] ! [%] ! [%] ![Step]![m3/h]![m3/h]!
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
! 39 ! 27.2 ! 0 ! 100 ! 0 ! 0 ! 0 ! 0 ! 0 ! 3 ! 0 ! 0 !
! ! ! 0 ! 0 ! ! ! ! ! ! ! 0 ! !
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
RMR 17:06:08 16-AUG-1999/MO
A description of the various parameters can be found in the following documents:
CM2Z8303e "Process image BPS Point Types and Parameters" (FLN points) or
CM2Z8568en VISONIK Point Types and Parameter Description VVS20 (alphabetical)
The selective system report SYR /G is a valuable aid.
Enter "syr /g=74", for example, to list all points allocated to Room 74 @TCR74:
syr /g=74
SYR 17:06:21 16-AUG-1999/MO
!FI TCR $d070'TCR74 (T39)
16-AUG-1999 17:04:18 AOPST=0
!FI AO $d070'AO39'29 iFanSpdSta
01-JAN-1993 00:00:00 AO=3 OPSTA=1
SYR 17:06:21 16-AUG-1999/MO
Operating the
data points
RMR report output
Example of an RMR
Meaning of the
p
arameter
s