User Manual

78/90
Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Engineering 12.06.2006
NIDES.RX
BPS
NV Name
(Description)
SNVT_Type NV Element
Link point Integration
function
nviSwitch24
SNVT_switch
State
@AI x '22
Value
@AI x '21
nviSwitch25
SNVT_switch
State
@AI x '24
Value
@AI x '23
nviTempP10
SNVT_temp_p
@AI x '17
nviTempSensor
SNVT_temp_p
@AI x '96 3.2.21
nviTempSensorPPS
SNVT_temp_p
@AI x '16 3.2.21
nviTerminalLoad
SNVT_lev_percent
@AI x '62 3.2.20
nviUnitStatus SNVT_hvac_status in_alarm
@AI x '49
*)
mode
@AI x '43 3.2.19
nviVol1
SNVT_vol
@AI x '151 AppLibV2
nviVolF1
SNVT_vol_f
@AI x '152 AppLibV2
nviVolt
SNVT_volt
@AI x '154 AppLibV2
nviVoltAc1
SNVT_volt_ac
@AI x '156 AppLibV2
nviVoltF1
SNVT_volt_f
@AI x '158 AppLibV2
*) Value 6W41) for FNC 10 or FNC 12:
With this binding, a frost alarm for the room can be realized.
If in_alarm=0, @Ai x '49 will show the value 6.
If in_alarm=1, @Ai x '49 will show the value 4.
@Ai x '49.LOL has to be set accordingly.
.
.
.
.
.
.
.
.
.