NIDES.RX
BPS
NV Name
(Description)
SNVT_Type NV Element
Link point Integration
function
nvoAirflowSetpt
SNVT_flow
@AO x ' 19
nvoApplicMode
SNVT_hvac_mode
@AO x ' 26 3.2.4
nvoAuxHeatEnable
SNVT_switch
Value
@AO x ' 30 3.2.23
nvoCount_1
SNVT_count
@AO x ' 99
nvoCount_2
SNVT_count
@AO x ' 100
nvoCtrl_Q14
SNVT_switch
State
@AO x ' 141
nvoCtrl_Q24
SNVT_switch
State
@AO x ' 143
nvoCtrl_Q34
SNVT_switch
State
@AO x ' 145
nvoCtrl_Y1
SNVT_switch
State
@AO x ' 133
nvoCtrl_Y2
SNVT_switch
State
@AO x ' 135
nvoCtrl_Y3
SNVT_switch
State
@AO x ' 137
nvoCtrl_Y4
SNVT_switch
State
@AO x ' 139
nvoCtrl_Y5
SNVT_switch
State
@AO x ' 20
nvoCtrl_Y6
SNVT_switch
State
@AO x ' 36
nvoEconEnable
SNVT_switch
State
@AO x ' 33
nvoEmergOverride
SNVT_hvac_emerg
@AO x ' 42
nvoEnergyHoldOff
SNVT_switch
State
@AO x ' 35
nvoExMod_1_Q14
SNVT_switch
State
@AO x ' 147
nvoExMod_1_Q24
SNVT_switch
State
@AO x ' 149
nvoExMod_1_Q34
SNVT_switch
State
@AO x ' 151
nvoExMod_1_Q44
SNVT_switch
State
@AO x ' 153
nvoExMod_2_Q14
SNVT_switch
State
@AO x ' 155
nvoExMod_2_Q24
SNVT_switch
State
@AO x ' 157
nvoExMod_2_Q34
SNVT_switch
State
@AO x ' 159
nvoExMod_2_Q44
SNVT_switch
State
@AO x ' 161
nvoFanSpeedCmd
SNVT_switch
State
@AO x ' 29
nvoFhMode UNVT_fh_mode State
@AO x ' 189 AppLibV2
workmode
@AO x ' 190
nvoFlow_1 SNVT_flow
@AO x ' 94
nvoFlow_2 SNVT_flow
@AO x ' 95