User Manual
68/90
Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Engineering 12.06.2006
4.11.1 Mapping table for NIDES.RX outputs
The NV Name and SNVT_Type columns contain the names of the NIDES.RX outputs
in the order in which they appear in the NIDES.RX window of the Binding Template
Editor. The switch must be set so that the NIDES.RX window
(Target) is to the left
of the connecting arrow.
Outputs in the NIDES.RX window of the Binding Template Editor cannot be integrated
unless they are documented here.
In the case of structured NVs, a permanently defined selection of elements is mapped.
These are shown in the NV Element column (not visible in the NIDES.RX window). The
value range, unit and semantics are defined by the SNVT type and documented here.
The Link point column shows the associated address. The link point type is always
AO, and the output value is always the EMV of the link point.
The Integration function column contains a reference to the relevant subsection of
Section 3. NVs with this type of reference can only be integrated with third-party
devices. NVs with the reference AppLibV2 are available when use is made of
Application Library V2, and can be integrated as single value parameters.
NIDES.RX
BPS
NV Name
(Description)
SNVT_Type NV Element
Link point Integration
function
ncoLuxThrsOff_1
SNVT_lux
← @AO x ' 112
ncoLuxThrsOff_2
SNVT_lux
← @AO x ' 113
ncoOAMinPos
SNVT_lev_percent
← @AO x ' 68
ncoSetpoints
SNVT_temp_setpt
occupied_cool
← @AO x ' 62 3.2.11
occupied_heat
← @AO x ' 65 3.2.11
standby_cool
← @AO x ' 63 3.2.11
standby_heat
← @AO x ' 66 3.2.11
unoccupied_cool
← @AO x ' 64 3.2.11
unoccupied_heat
← @AO x ' 67 3.2.11
ncoVolSetpt
UNVT_vol_setpt
MaxDischAirFlow
← @AO x ' 188 AppLibV2
MaxFlow
← @AO x ' 182
MaxFlowHeat
← @AO x ' 183
MinFlow
← @AO x ' 184
MinFlowEco
← @AO x ' 185
MinFlowHeat
← @AO x ' 186
MinFlowStby
← @AO x ' 187