Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Engineering 12.06.2006
4.10.2 Lighting and blind group priorities
The following rules apply to the priorities:
– Each group of blinds and each lighting group must be assigned a priority level
between 1 and 100, where 1 is the highest.
– No priority level may be assigned more than once (this applies to lighting and blinds
separately).
– The priorities assigned are relevant only if the group concerned is configured in
“Remote” mode.
– In "Remote" mode, if two groups with the same priority act on the same controllers,
the last command always applies.