User Manual
64/90
Building Technologies Integration of DESIGO™ RXC CM2Z8338en_01
Building Automation Engineering 12.06.2006
4.10.1 Edited GroupConfig.COL for the example
The print-out below shows the GroupConfig.COL file, after editing for the system
example described above. The edited text is shown in bold. Refer to the previous page
for notes on the entries.
.TSK112
1 -- [1-08-99/V1.8/fl] RX-Master: Konfigurations-
990 -- HVAC group ******************************************************
991 ; -- Format: DATA group number,room number,room number,room number,-9
992 ; -- DATA group number,room number,room number,room number,-9
993 ; -- DATA -9
994 ; -- Range: group number --> 1..200
995 ; -- room number --> 1..99
996 ; -- ****************************************************************
1000 DATA 1,5,-9
1010 DATA 2,1,2,3,4,-9
1020 DATA -9
1990 -- TED group (Energy demand)*********************************************
1991 ; -- Format: DATA group number,EFORM,regulator number,regulator number,-9
1992 ; -- DATA group number,EFORM,regulator number,regulator number,-9
1993 ; -- DATA -9
1994 ; -- Range: group number --> 1..200
1995 ; -- EFORM --> 0..31
1996 ; -- regulator number --> 33..126
1997 ; -- ********************************************************************
2000 DATA 1,0,33,34,35,36,-9
2010 DATA 2,1,33,34,35,36,-9
2020 DATA 3,0,37,38,39,40,41,42,-9
2030 DATA 4,1,37,38,39,40,41,42,-9
2040 DATA -9
2990 -- Blind group ************************************************************
2991 ; -- Format: DATA group number,priority,regulator number,regulator number,-9
2992 ; -- DATA group number,priority,regulator number,regulator number,-9
2993 ; -- DATA -9
2994 ; -- Range: group number --> 1..100
2995 ; -- priority --> 1..100
2996 ; -- regulator number --> 33..126
2997 ; -- ***********************************************************************
3000 DATA 1,5,33,34,35,36,-9
3010 DATA 2,6,43,44,-9
3020 DATA 3,4,33,34,35,36,43,44,-9
3030 DATA 4,2,37,38,39,40,41,42,-9
3040 DATA 5,3,42,44,-9
3050 DATA 6,1,33,34,35,36,43,44,37,38,39,40,41,42,-9
3060 DATA -9
3990 -- Light group ************************************************************
3991 ; -- Format: DATA Group number,priority,regulator number,regulator number,-9
3992 ; -- DATA Group number,priority,regulator number,regulator number,-9
3993 ; -- DATA -9
3994 ; -- Range: Group number --> 101..200
3995 ; -- priority --> 1..100
3996 ; -- regulator number --> 33..126
3997 ; -- ***********************************************************************
4000 DATA 101,3,33,34,35,36,-9
4010 DATA 102,4,43,44,-9
4030 DATA 103,2,37,38,39,40,41,42,-9
4000 DATA 104,1,33,34,35,36,43,44,37,38,39,40,41,42,-9
4040 DATA -9
4996 -- TTY interface to NIDES.RX **********************
4997 ; -- Format: 1 --> TTY1, 2 --> TTY2 oder -9 --> TTY1
4998 ; -- ***********************************************
5000 DATA -9
EXIT
Entries in
GroupConfig.COL