Building Automation Engineering 12.06.2006
4.9 Defining groups
The groupings are defined in file GroupConfig.COL by editing TSK112 manually
(assuming it exists; if not, it must be created). In this task the “RX coupling” application
later creates the VISONIK data structures automatically.
The print-out below shows the default TSK112 with details of the format for each of the
groups. For editing and saving the GroupCOnfig.COL file, we recommend use of the
VISOTool, because in the BPS the comments are removed when the file is saved. The
arrows in the left margin point to the first input line of each "group category" (HVAC
groups, lighting groups etc.)
⇒
⇒
⇒
⇒
⇒
.TSK112
1 -- CFE-NIDES.RX, V2.0 : Group Configuration
100 NewG:=1
110 END
;990 HVAC groups *****************************************************
;991 Format: DATA group number,room number,room number,room number,-9
;992 DATA group number,room number,room number,room number,-9
;993 DATA -9
;994 Ranges: group number --> 1..200
;995 room number --> 1..99
;996 *****************************************************************
1000 DATA -9
;1990 TED groups (Energy demand) *************************************
;1991 Format: DATA group number,EFORM,regulator number,regulator number,-9
;1992 DATA group number,EFORM,regulator number,regulator number,-9
;1993 DATA -9
;1994 Ranges: group number --> 1..200
;1995 EFORM --> 0..31
;1996 regulator number --> 33..126
;1997 ****************************************************************
2000 DATA -9
;2990 Blind groups ***************************************************
;2991 Format: DATA group number,priority,regulator number,regulator number,-9
;2992 DATA group number,priority,regulator number,regulator number,-9
;2993 DATA -9
;2994 Ranges: group number --> 1..100
;2995 priority --> 1..100
;2996 regulator number --> 33..126
;2997 ****************************************************************
3000 DATA -9
;3990 Light groups ***************************************************
;3991 Format: DATA Group number,priority,regulator number,regulator number,-9
;3992 DATA Group number,priority,regulator number,regulator number,-9
;3993 DATA -9
;3994 Ranges: Group number --> 101..200
;3995 priority --> 1..100
;3996 regulator number --> 33..126
;3997 ****************************************************************
4000 DATA -9
;4996 TTY interface to NIDES.RX **************************************
;4997 Format: 1 --> TTY1, 2 --> TTY2 or -9 --> TTY1
;4998 ****************************************************************
5000 DATA -9
EXIT
Introduction
Default TSK112