User Manual

57/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Engineering 12.06.2006
4.6.1 Content and format of the location text
The location text must always include the following information:
- Number of the room in which the controller is located
- Information as to whether the controller in that room is a master or slave (HVAC)
- VISONIK RXC device number (identification of the device in the VISONIK system)
Note:
The location text does not necessarily correspond to the building-based addresses.
These can be entered later with the appropriate text in the TEC data point.
The format of the location text for the integration of RXC controllers into VISONIK is as
follows:
rrMccc or rrSccc
Character Description Value range
Note
rr Room number 1 ... 99 1 or 2 digits from the VISONIK TEC
address range (limited here to 1 …
99)
M
Master controller
There is always 1 HVAC master
controller in the room
S
Slave controller
Apart from the master controller, all
the RXC controllers in the room are
slave controllers (max. 9 slaves
allowable)
ccc
RXC controller
number
33 ...126 2 or 3 digits from the VISONIK TEC
address range
The format of the location text for the integration of third-party devices is:
rr Room number 1 ... 99
X Identifies devices as a third-party device
ccc Device number 128 ... 255
Example: 47X163
Do enter leading zeros for the location text in the RXT10, otherwise the RX master
(CFE application) will not run.
Example:
Enter “1M50” – not “01M050”.
See also the location text entries for the example on the next page.
All RXC applications have HVAC functions. Some
– have no lighting and blind functions, while others
do have lighting and blind functions
The allocation of M or S in the location text field is determined only by the HVAC
functions of the application.
Contents
Format
Format for third-party
devices
N.B.: No leading zero!
Note on M and S