4.6 Entering the location text in the RXT10
When integrating DESIGO RXC into VISONIK, the “Location” input field in the RXT10 is
used for additional VISONIK-specific information about the room number, master/slave
controller and RXC controller number. This information is referred to as the “location
text”. It can be entered in the following places, depending on the activity being carried
out:
– In the “Device” menu, when adding a new device
– In the “List View” menu when creating new devices by copying and modifying
identical applications or when editing the data at a later stage.
The information entered is needed by the conversion tool (a component of the RXT10
tool) to create the relevant VISONIK data structures.
The screenshot below shows the “Overview” tab after selection of the “Device” / “Add”
menu.
The location text “1M50” for the new devices has been entered in the “Location” field:
8338Z26E
The screenshot below shows the situation in the “List View” after copying and adding
the newly created device using the options “Device” / “Copy”, “Device” / “Add”.
8338O01E
The location text and room number were then edited in the relevant fields
to 10M111/Room 10:
8338O02E
The RxNIBPS.COL file is created whenever the project is saved. In the event of
changes, such as the later re-allocation of rooms, the changes must also be edited in
the RXT10 and a new RxNIBPS.COL file must be generated by saving the new data.
Purpose of the location
text in the RXT10
Input under “Add
devices”
Input under “Copy
devices”
Modifications:
IMPORTANT NOTE