Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Engineering 12.06.2006
4.2 From the application to the TEC data points
The diagram below is a simplified illustration of the route taken by data from the I/Os
and parameters of the application through to the VISONIK data points in the BPS. Its
purpose is
To provide an overall picture of the data flow, from the perspective of the application
To illustrate the interaction between the various elements.
This will help clarify the engineering steps described later.
NIDES Binding Template
1 2 3 8
RSDP
Link points
RSDP
RSDP
RSDP
RSDP
RSDP
RSDP
RSDP
Device
DESIGO RXC
LON (LonMark)
BPS
NIDES.RX
I/Os Parameters
Application
1 2
1 2 3 6
Process image
Infolist
TEC
data points
T
Room temp.
T
R
nvoSpaceTemp
RSUZx
oSpaTmp
@TCRx.RRTP
NVs
Parameters
100
0
SpH SpC TR [°C]
YH YC
HC
Y [%]
VISONIK
data points
BLN
(SDLC)
I/Os
RSDPs
NVs
8338Z23E
Room
P
arameters
project
NVs
Operation
The data flow is indicated in the left of the diagram from the bottom to the top, using a
room temperature T
R
as an example. Data is, of course, also transmitted from the top
down (e.g. setpoints).
Purpose of the overview
Note