3.5 Control priority functions for lighting
and blind groups
Since one RXC controller can be assigned to a number of lighting or blind groups, each
with different group values, a method must be found to determine which group is to act
on the RXC controller. The diagram below highlights the problem on the basis of the
groupings illustrated earlier.
If, for example, a command applies to group Aop, this will transmit the command to the
associated RXC controllers, including RXC controllers 1, 2, 6 and 7. At the same time,
however, group AOx also acts on these controllers. How is this resolved?
RXC 1, 2, 6, 7
RXC 3..5, 8..10
RXC 11, 12
RXC 13, 15
&
AOp
AOx
AOw
AOy
AOp
AOw
AOp
AOp
8338Z36E
&: Rules for bindings
&
&
&
The problem described above is solved as follows:
Assign priorities to the blind and lighting groups.
When a controller belongs to several groups of the same priority, the last command
always takes precedence.
Problem
Solution