User Manual

44/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.29 Additional single parameters for HVAC control
Depends on application
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element
Function/Range
BT
User designation NV name NV
element
@AOx’19.EMV Volume flow setpoint nvoAirflowSetpt l/s ne
Aiflow Setpoint
nviAirflowSetpt
@AOx’25.EMV Occupancy sensor nvoOccSensor 0 = Occupied, 1 = Unocc. ne
Occup Sensor
nviOccSensor
@AOx’27.EMV
Definition of sequence:
heating/cooling
nvoHeatCool 0 = Auto, 1 = Heat, 3 = Cool ne Heat Cool Mode nviHeatCool
@AOx’29.EMV
Definition of fan speed
nvoFanSpeedCmd
0 = Off, 1 = St.1, 2 = St. 2,
3 = St.3, 4 = Auto
ne
Fan Speed Command
nviFanSpeedCmd
@AOx’33.EMV
Economizer enable (fan coil)
nvoEconEnable . state 0 = OFF, 1 = ON ne Economiser Enable nviEconEnable State
@AOx’35.EMV
Energy hold-off
nvoEnergyHoldOff . state 0 = OFF, 1 = ON ne
Energy Hold-off
nviEnergyHoldOff State
@AOx’43.EMV
Temperature of primary medium
nvoSourceTemp °C ne Source Temp nviSourceTemp
@AOx’44.EMV
Outdoor temperature
nvoOutdoorTemp °C ne
Outdoor Temp
nviOutdoorTemp
@AOx’45.EMV
Indoor air humidity
nvoSpaceRH % rh ne Space Humidity nviSpaceRH
@AOx’46.EMV
CO
2
concentration in room
nvoSpaceCO2 ppm ne
Space CO2
nviSpaceCO2
@AOx’47.EMV
Dewpoint temperature of indoor air
nvoSpaceDewPt °C ne Space Dewpoint nviSpaceDewPt
@AOx’48.EMV
Dewpoint temp. of outdoor air
nvoOutdoorDewPt °C ne
Outdoor Dewpoint
nviOutdoorDewPt
@AOx’53.EMV
Temp. of primary heating medium
nvoSourceTempH °C ne
Source Temp Heating
nviSourceTempH
@AOx’68.EMV Min. outside air damper position ncoOAMinPos % ne
Outs. Air Dmp Min Pos
nciOAMinPos
@AIx’13.EMV
CO
2
concentration in room
nviSpaceCO2 ppm ne
Space CO2
nvoSpaceCO2
@AIx’42.EMV Current setpoint nviEffectSetpt °C ne
Effect Setpt
nvoEffectSetpt
@AIx60’.EMV Supply air temperature nviDischAirTemp °C ne Discharge Air Temp nvoDischAirTemp
@AIx’66.EMV Position of outside air damper nviOADamper 0 ... 100 % ne
Outdoor Air Damper
nvoOADamper
@AIx’67.EMV Indoor air humidity nviSpaceRH % rh ne Space Humidity nvoSpaceRH
@AIx’68.EMV
Dew point monitoring
nviSpaceDewPt
50°C = Normal,
-10°C = Condensation
ne
Space Dewpoint
nvoSpaceDewPt
@AIx’81.EMV Local occupancy sensor nviOccSensor
0 = Unoccupied
1 = Occupied
ne
Local Occup Sensor
nvoOccSensor
@AIx’82.EMV Volume flow temperature nviFlowTemp °C ne Flow Temp nvoFlowTemp
@AIx’83.EMV Pump status nviPumpStatus. value 0 = Off, 0.5...100% = On ne
Pump Status
nvoPumpStatus Value