User Manual

43/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.28 Lighting control, 4 groups
INT02, INT03, INT06, INT07, INT11
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element
Function/Range
BT
User designation NV name NV
element
@AOx’5.EMV nvoLightOverr_1
0 = OFF; 1 = ON, 255 =
Auto
1
Light Override #1
nviLightOverr_1
@AOx‘5.PARINT(2) nvoLightCmd_1 0 = Off, 0.5...100 = On, n%
ne
Light Command #1 nviLightCmd_1
@AOx’6.EMV nvoLightCmd_2 0 = Off, 0.5...100 = On, n%
ne
Light Command #2
nviLightCmd_2
@AOx‘6.PARINT(2)
Control of lighting groups 1 and 2
(see diagram)
@AOx’7.EMV nvoLightOverr_2
0 = OFF; 1 = ON, 255 =
Auto
1
Light Override #2
nviLightOverr_2
@AOx‘7.PARINT(2) nvoLightCmd_3 0 = Off, 0.5...100 = On, n%
ne
Light Command #3 nviLightCmd_3
@AOx’8.EMV nvoLightCmd_4 0 = Off, 0.5...100 = On, n%
ne
Light Command #4
nviLightCmd_4
@AOx‘8.PARINT(2)
Control of lighting groups 3 and 4
(See diagram)
AOx’5.FBV
Current lighting value Gp1
nviLightCmd_1. value 0 = Off, 0.5...100 = On, n%
1
Light Command #1 nvoLightCmd_1 Value
AOx’6.FBV
Current lighting value Gp2
nviLightCmd_2 . value 0 = Off, 0.5...100 = On, n%
1
Light Command #2
nvoLightCmd_2 Value
AOx’7.FBV
Current lighting value Gp3
nviLightCmd_3 . value 0 = Off, 0.5...100 = On, n%
1
Light Command #3 nvoLightCmd_3 Value
AOx’8.FBV
Current lighting value Gp4
nviLightCmd_4 . value 0 = Off, 0.5...100 = On, n%
1
Light Command #4
nvoLightCmd_4 Value
Light
Command 1
AOx’5.FBV AOx’6.FBV
Present value
Lighting zone 1
Present value
Lighting zone 2
Lighting command 1
AOx’5.EMV * AOx’6.EMV *
Override for
Lighting zones 1 & 2
AOx’5.PARINT(2)
OR
AOx’6.PARINT(2)
Auto
S1=Local
S1=Remote
S2=Local
S2=Remote
S3=local
S1
S2
S3
RX-Master
Light
Command 2
Light
Override 1
Light
Command 1
Light
Command 2
Lighting command 2
01149en A
AOx'7.EMV* AOx'8.EMV* AOx'7.FBV AOx'8.FBV
AOx'7.PARINT(2)
OR
AOx'8.PARINT(2)
Lighting
command 3
Lighting
command 4
Lighting
override 2
Lighting
command 4
Lighting
command 3
Auto
S1 S2 S3
Override for
lighting Zones 3&4
Lighting
command 3
Lighting
command 4
Current value
lighting zone 3
S3=Local
S1=Local
S2=Local
S2=Remote
S1=Remote
01150en
RX master
Current value
lighting zone 4