User Manual
42/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.27 Lighting control, 2 groups
INT01, INT04, INT05, INT10, INT12, INT15, INT17
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name NV element
@AOx’5.EMV → nvoLightOverr_1 0 = OFF; 1 = ON, 255 = Auto → 1
Light Override #1
nviLightOverr_1
@AOx‘5.PARINT(2)
Control of lighting group 1
(see diagram)
→ nvoLightCmd_1 0 = Off, 0.5...100 = On, n% →
ne
Light Command #1 nviLightCmd_1
@AOx’6.EMV → nvoLightOverr_2 0 = OFF; 1 = ON, 255 = Auto → 1
Light Override #2
nviLightOverr_2
@AOx‘6.PARINT(2)
Control of lighting group 2
(see diagram)
→ nvoLightCmd_2 0 = Off, 0.5...100 = On, n% →
ne
Light Command #2 nviLightCmd_2
AOx’5.FBV
Current lighting value, Gp 1
←
nviLightCmd_1. value
0 = Off, 0.5...100 = On, n% ←
1
Light Command #1
nvoLightCmd_1
Value
AOx’6.FBV
Current lighting value, Gp 2
←
nviLightCmd_2. value
0 = Off, 0.5...100 = On, n% ←
1
Light Command #2
nvoLightCmd_2
Value
AOx'5.EMV*
AOx'6.EMV* AOx'5.FBV AOx'6.FBV
Auto
Auto
S4
S1
S2
S3
AOx'5.PARINT(2)
AOx'5.PARINT(2)
Lighting
command 1
Lighting
command 2
Lighting override 1
Lighting override 2
Lighting
command 1
Lighting
command 2
Override for
lighting zone 1
Lighting
command 2
Current value
lighting zone 1
Lighting
command 1
Current value
lighting zone 2
RX master
S4=Local
S1=Local
S1=
Remote
S2=Local
S2=
Remote
S3=Local
Override for
lighting zone 2
01148en
.
Note
If the standard binding templates are used (
nviLightCmd_y) not
integrated), the lighting is controlled in ”Local“ mode as follows:
f a new value is written to @AOx’y.EMV, the CFE software
switches briefly to “Remote” and transmits the relevant command
to the NV “Light Override y”. It then reverts automatically to
“Local”.