User Manual

41/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.26 Control of blinds, 4 groups
INT05
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name NV element
@AOx’1.EMV nvoSblndOverr_1 0=Up; 1=Down1; 2=Down2, 3=Auto 1
Blind Override #1
nviSblndOverr_1
@AOx‘1.PARINT(2) nvoSblndCmd_1 0 = Up; 1 = Down1; 2 = Down2
ne
Blind Command #1 nviSblndCmd_1
@AOx’2.EMV nvoSblndCmd_2 0 = Up; 1 = Down1; 2 = Down2
ne
Blind Command #2
nviSblndCmd_2
@AOx‘2.PARINT(2)
Control of Blinds 1 and 2
(See diagram)
@AOx’3.EMV nvoSblndOverr_2 0=Up; 1=Down1; 2=Down2, 3=Auto 1
Blind Override #2
nviSblndOverr_2
@AOx‘3.PARINT(2) nvoSblndCmd_3 0 = Up; 1 = Down1; 2 = Down2
ne
Blind Command #3 nviSblndCmd_3
@AOx’4.EMV nvoSblndCmd_4 0 = Up; 1 = Down1; 2 = Down2
ne
Blind Command #4
nviSblndCmd_4
@AOx‘4.PARINT(2)
Control of Blinds 3 and 4
(See diagram)
AOx’1.FBV
Current position of Blind 1
nviSblndCmd_1 . setting 0 = Fully open... 100 = Fully closed
1
Blind Command #1 nvoSblndCmd_1 Setting
AOx’2.FBV
Current position of Blind 2
nviSblndCmd_2 . setting 0 = Fully open... 100 = Fully closed
1
Blind Command #2
nvoSblndCmd_2 Setting
AOx’3.FBV
Current position of Blind 3
nviSblndCmd_3 . setting 0 = Fully open... 100 = Fully closed
1
Blind Command #3 nvoSblndCmd_3 Setting
AOx’4.FBV
Current position of Blind 4
nviSblndCmd_4 . setting 0 = Fully open... 100 = Fully closed
1
Blind Command #4
nvoSblndCmd_4 Setting
01146de
Blind
Command 1
AOx’1.FBV AOx’2.FBV
Aktuelle Stellung
Jalousie 1
Aktuelle Stellung
Jalousie 2
Jalousiebefehl 1 Jalousiebefehl 2
AOx’1.EMV AOx’2.EMV
Overrider
Jalousien 1 & 2
AOx’1.PARINT(2)
OR
AOx’2.PARINT(2)
Auto
S1=Lokal
S1=Fern
S2=Lokal
S2=Fern
S3=lokal
S1
S2
S3
RX-Master
Blind
Command 2
Blind
Override 1
Blind
Command 1
Blind
Command 2
Blind
Command 3
AOx’3.FBV
AOx’4.FBV
Aktuelle Stellung
Jalousie 3
Aktuelle Stellung
Jalousie 4
Jalousiebefehl 3
Jalousiebefehl 4
AOx’3.EMV AOx’4.EMV
Overrider
Jalousien 3 & 4
AOx’3.PARINT(2)
OR
AOx’4.PARINT(2)
Auto
S1=Lokal
S1=Fern
S2=Lokal
S2=Fern
S3=lokal
S1
S2
S3
RX-Master
Blind
Command 4
Blind
Override 2
Blind
Command 3
Blind
Command 4
01147de