User Manual

40/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.25 Control of blinds, 2 groups
INT01, INT02, INT03, INT04, INT06, INT07, INT15, INT17
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element
Function/Range
BT
User designation NV name NV
element
@AOx’1.EMV nvoSblndOverr_1 0=Up; 1=Down1; 2=Down2, 3=Auto 1
Blind Override #1
nviSblndOverr_1
@AOx‘1.PARINT(2)
Control of Blind 1
(See diagram)
nvoSblndCmd_1 0 = Up; 1 = Down1; 2 = Down2
ne
Blind Command #1
nviSblndCmd_1
@AOx’2.EMV nvoSblndOverr_2 0=Up; 1=Down1; 2=Down2, 3=Auto 1
Blind Override #2
nviSblndOverr_2
@AOx‘2.PARINT(2)
Control of Blind 2
(See diagram)
nvoSblndCmd_2 0 = Up; 1 = Down1; 2 = Down2
ne
Blind Command #2
nviSblndCmd_2
AOx’1.FBV
Current position of Blind 1
nviSblndCmd_1. setting
0 = Fully open... 100 = Fully closed
1
Blind Command #1 nvoSblndCmd_1
Setting
AOx’2.FBV
Current position of Blind 2
nviSblndCmd_2. setting
0 = Fully open... 100 = Fully closed
1
Blind Command #2
nvoSblndCmd_2
Setting
AOx'1.EMV AOx'2.EMV AOx'1.FBV AOx'2.FBV
Auto
Auto
S4S1
S2 S3
AOx'1.PARINT(2)
AOx'2.PARINT(2)
Blinds
command 1
Blinds
command 2
Blinds override 1 Blinds override 2
Blinds
command 1
Blinds
command 2
Override for
blind 1
Blinds
command 2
Current pos.
blind 1
Blinds
command 1
Current pos.
blind 2
RX master
S4=Local
S1=Local
S1=
Remote
S2=Local
S2=
Remote
S3=Local
Override for
blind 2
01145en
Ab1 = Jalousie geschlossen, Lamellen geöffnet
Ab2 = Jalousie geschlossen, Lamellen geschlossen
Note
If the standard binding templates are used (
nviSblndCmd_y) not
integrated), the blinds are controlled in ”Local“ mode as follows:
If a new value is written to @Aox’y.EMV, the CFE software
switches briefly to “Remote” and transmits the relevant command
to the NV “Blind Override y”.
It then automatically reverts to “Local”.