User Manual
39/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.24 Intranet room operation
All RXC applications
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name
@TCRn.AOPST See "Effective room status" ← nviEffectOccup
See "Effective room status"
←
1
Effect Occup
nvoEffectOccup
@TCRy.ARTP Current room temperature ← nviSpaceTemp Current room temperature ←
1
Effect Space Temp nvoSpaceTemp
@AOx’24.EMV
Room status: 0 = Occupied
3 = Standby
→ nvoOccManCmd
Operating mode on room unit → *
)
Occup Override
nviOccManCmd
@AOx’12.EMV
Sollwertkorrektur: -3 ... +3 °C
→ nvoSetptOffset
Setpoint adjustment from
room unit
→ *
)
Setpt Offset nviSetptOffset
@AIx’80.EMV
Actual setpoint adjustment
← nviSetptOffset Actual setpoint adjustment ← *
)
Local Setpt Offset nvoSetptOffset
*) The Intranet room operation feature has its own standard binding template, which integrates these three additional points.