Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
In operating state SOPST=6, Emergency Override is determined by link point @AOx’42. Single-parameter integration of iEmergOvr for the HVAC master in Room n with Controller
number x). The value of must always be assigned before
setting @TCRn.SOPST to 6.
Caution If the room concerned is subject to a time schedule(@DSTy), this must be deactivated during emergency operation (@DSTy.ACT=0), otherwise parameter
@TCRn.SOPST will be overwritten again.
3.2.23 Disable or limit auxiliary energy supply
RAD03, FNC01, FNC03, VAV03, VAV06, FPB05
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element
Function/Range
BT
User designation NV name NV element
@TCRn.RLELD
@TCRn.RLELD.OR
@TCRn.ELDLR
See diagram → nvoAuxHeatEnable . value
Enable auxiliary energy
0...100%
→
ne
Auxillary Heat Enable nviAuxHeatEnable Value
TCRn.RLELD TCRn.RLELD.OR TCRn.ELDLR
RLELD*100
Auxiliary heat enable
S1
S1=1 S1=0
Disable aux. energy
Switch to disable
aux. energy
active
Limit aux. energy
RX master