3.2.22 Definition of emergency mode (Emergency OFF / Smoke extraction)
All VAV applications, FPB05
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element
Function/Range
BT
User designation NV name
@AOx’42.EMV
@TCRn.SOPST
See table of bindings
→ nvoEmergOverride
See table of bindings
→ ne Emergency override nviEmergOverride
Table of bindings
@AOx’42.EMV @TCRn.SOPST
Emergeny Override Description
x
5 = Smoke
extraction
Ö
3 = EMERG_PURGE All dampers fully open
0
6 = Emergency
OFF
Ö
4 = EMERG_SHUTDOWN All dampers closed
1
6 = Emergency
OFF
Ö
1 = EMERG_PRESSURIZE
Supply air damper(s) fully open, extract air damper
closed
2
6 = Emergency
OFF
Ö
2 = EMERG_DEPRESSURIZE
Supply air damper(s) closed, extract air damper fully
open