User Manual

31/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.13 Display current fan speed
All FNC applications
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name
@TCRn.OFAN Fan speed
nviFanSpeed
0 = Off, 1 = Sp.1, 2 =
Sp.2,
3 = Sp.3
2
Fan Speed nvoFanSpeed
3.2.14 Electric heating coil, position of current valve and max. electrical energy
RAD03, FNC01, VAV03, VAV06, FPB05
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name
@TCRn.FCHB
Max. electrical energy
(see diagram)
nviLoadAbs Heating output in watts
2
Absolute Power Cons. nvoLoadAbs
@TCRn.OHHB(x)
Position of current valve,
controller x
nviHeatPrimary
Position of primary
heating valve
2
Primary Heat nvoHeatPrimary
3.2.15 Electric reheater, position of current valve and max. electrical energy
FNC03
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name
@TCRn.FCHB
Max. electrical energy
(see diagram)
nviLoadAbs Heating output in watts
2
Absolute Power Cons. nvoLoadAbs
@TCRn.OHHB(x)
Position of current valve,
controller x
nviHeatSecondary
Position of secondary
heating valve
2
Secondary Heat nvoHeatSecondary